What this guide works from. One rig: an EG4 6000XP, a DIY 16-cell LiFePO4 pack, 280 Ah, with a JK BMS that has no link the 6000XP can read. The screen shows W000. The pack rests at 52.6 V. The BMS app shows 44% charge.
The short answer. Yes. If your pack has no BMS comms, set an EG4 6000XP or 18kPV to Lead-Acid battery type and run it on voltage. BMS means battery management system, the board that guards the cells. Comms means the data link between the BMS and the inverter. For 16S LiFePO4, set CV to 55.2 V, float to 53.6 V, and the low cut-off to 48.0 V. CV is the top charge volt, and float is the lower hold volt after the pack is full. For 15S, use 51.75 V bulk, 50.25 V float, and 45.0 V cut-off. Change the 6000XP CV stock value of 56.4 V, because it sits above the 16S bulk target. Voltage mode only works if the inverter backs off before the BMS has to trip.
The rig that kept dropping out
The pack was a DIY build: 16 LiFePO4 cells, 280 Ah, a JK BMS on top. The 6000XP was set to Lithium, brand number 1, and the screen showed W000, Warning 00, “Communication failure with battery”. The link would come up for a few minutes, then drop. Each drop cut the output. The house lost power at random hours. The app showed all 16 cells between 3.28 V and 3.30 V, and 44% charge. The fault was the link, not the pack.
So we stopped chasing the link and switched to voltage mode that night. Setting 3 to Lead-Acid, Setting 7 CV to 55.2 V, Setting 8 float to 53.6 V, Settings 11 and 12 cut-off to 48.0 V. The dropouts stopped the same night. The next morning the pack climbed from 51.8 V toward bulk. At 11:05 a.m. it hit 55.2 V, and the charge current tapered from 60 A down to 6 A. At noon it dropped to float at 53.6 V. The app showed all 16 cells between 3.44 V and 3.46 V, and 100% charge. That evening the pack fell to 49.6 V at 9:40 p.m. and the inverter moved the loads to grid. The BMS never cut. The screen SOC read 58%. The app read 24%. The screen was guessing from volts. The app was counting amps.

What voltage mode really is
In voltage mode the inverter charges and drains by voltage alone. It gets no state of charge, no charge current limit, and no cell volts from the BMS. State of charge, or SOC, is how full the battery is, in percent. The BMS is still in the loop and still guards the pack. A high cell can cut charge. A low cell can cut discharge. In closed loop the BMS sets the normal limits. In voltage mode, you set them.
The 18kPV manual v1.2.0 says it in plain words: pick the “Lead-Acid” setting if the lithium battery cannot talk to the inverter. You are not telling the inverter your pack is lead-acid. You are telling it to stop waiting for BMS data and run on voltage. The cells on the bus are still lithium. The battery type is just the switch that turns comms off and voltage control on.
The check that counts is whether voltage rises on charge, falls on discharge, and stops where you told it to stop. Voltage mode keeps the house running while you sort out a cable, a protocol, or a BMS that will not link. See the closed vs open loop guide for the trade-off: closed loop is better when it works, because the BMS slows charge current as the pack fills.
The settings: 16S and 15S kept separate
This is the one table in this article you must not mix up. Do not mix the rows. A 15S pack and a 16S pack run at different volts, and a setting safe for one is wrong for the other. Count your cells first, in the BMS app or on the pack build sheet. 16S means 16 cells in a row, and 15S means 15.
| Pack | Bulk / CV volt | Float volt | Low cut-off volt |
|---|---|---|---|
| 16S LiFePO4 | 55.2 V (3.45 V per cell) | 53.6 V (3.35 V per cell) | 48.0 V (3.00 V per cell) |
| 15S LiFePO4 | 51.75 V (3.45 V per cell) | 50.25 V (3.35 V per cell) | 45.0 V (3.00 V per cell) |
Per-cell values match in both rows: bulk 3.45 V, float 3.35 V, cut-off 3.00 V. Set CV, Setting 7 on the 6000XP, to the bulk value for your cell count, not the 56.4 V stock value. Turn equalization off and set temp comp to 0 mV/C. Equalization is a lead-acid top-up stage that lifts volt high to stir the acid, and it does not belong on lithium. Temp comp shifts charge volt with heat, which is a lead-acid trait too, so set it to zero. Keep charge current at 0.3C or less. 0.3C means 0.3 times the pack size: 30 A on a 100 Ah pack, 60 A on 200 Ah, 84 A on 280 Ah. Keep the BMS low-volt cut below the inverter cut-off: 44.8 to 46.4 V for 16S, and 42.0 to 43.5 V for 15S.

The 6000XP menus, setting by setting
These setting numbers come from the manual, and they are the checked ones for the 6000XP.
Setting 3 is Battery. Set it to Lead-Acid, the switch into voltage mode, and enter the real size in amp hours when asked. Amp hours, or Ah, is how much charge the pack holds. Setting 7 is CV volt, range 50 to 59 V, stock 56.4 V, in lead-acid mode only: set it to 55.2 V for 16S and 51.75 V for 15S. Setting 8 is float volt, range 50 to 56 V, stock 54 V, in lead-acid mode only: set it to 53.6 V for 16S and 50.25 V for 15S.
Setting 6 is top charge current, range 0 to 125 A, stock 125 A, so set it to your 0.3C limit or less. The 6000XP spec lists a battery volt range of 46.4 to 60 V for lithium and 38.4 to 60 V for lead-acid, and a charge cut-off volt of 58.4 V. Setting 9 is top discharge current, range 10 to 140 A, stock 140 A, so set it no higher than the BMS discharge limit. Setting 10 is discharge control. In voltage mode, pick voltage.
Setting 11 is cut-off, stock 42 V, and Setting 12 is end of discharge, also stock 42 V. Set both to 48.0 V for 16S and 45.0 V for 15S. The 42 V stock value is far too low, since on a 16S pack it is 2.625 V per cell, below the point where the BMS should already have tripped.
| Setting | What it does | Stock value | Set it to (16S) | Set it to (15S) |
|---|---|---|---|---|
| 3 Battery | Battery type, the voltage mode switch. | Lithium | Lead-Acid | Lead-Acid |
| 6 Charge current | Top charge current. | 125 A | 84 A or less (0.3C) | 84 A or less (0.3C) |
| 7 CV volt | Top charge volt. | 56.4 V | 55.2 V | 51.75 V |
| 8 Float volt | Hold volt after full. | 54 V | 53.6 V | 50.25 V |
| 9 Discharge current | Top discharge current. | 140 A | BMS limit or less | BMS limit or less |
| 10 Discharge control | Cut on volts or on SOC. | SOC | Voltage | Voltage |
| 11 Cut-off | Low volt cut-off. | 42 V | 48.0 V | 45.0 V |
| 12 End of discharge | End of discharge volt. | 42 V | 48.0 V | 45.0 V |

Why the battery maker’s window governs
These settings are a safe fallback for a normal DIY LiFePO4 pack. They do not take the place of your own battery datasheet. If your battery maker gives a charge volt, a float volt, or a low cut-off, use those numbers. The maker’s window governs. The maker tested that exact cell and BMS. EG4’s own WallMount pack shows the shape of that answer. Its charge volt is 56.0 V, plus or minus 0.8 V. Its low DC cut-off is 44.8 V. Do not copy the WallMount numbers onto a DIY pack. The cells and BMS differ. The 58.4 V charge cut-off is a hard inverter limit, not a goal. If pack volt nears it, stop and find out why.
Why the cut-off moves with the load
Top pages list one fixed cut-off and stop there. The 6000XP spec sheet says the low-volt warning and cut-off shift with load. At light load, under 20%, the low DC warning sits at 44.0 V. At mid load it drops by 1.2 V, and at heavy load, 50% or more, it drops by 3.6 V. The cut-off moves the same way, and the cut-off return volt is 48 V when the cut-off sits below 45 V.
What this means in plain words: a fixed 48.0 V cut-off can trip early when a heavy load pulls the volt down for a short time. That dip is load sag, not an empty pack. The pack volt falls while the load runs, then springs back when the load stops. If your inverter cuts out under a heavy load while the pack still has charge, check the load-based warning and cut-off values in the spec sheet for your model. Set the cut-off with the load in mind, and keep the BMS low-volt cut below the inverter cut-off, as listed above.
| Load | Low DC warning | Cut-off shift | What it means |
|---|---|---|---|
| Light, under 20% | 44.0 V | No shift | Pack volt reads true. |
| Mid load | 42.8 V | Drops 1.2 V | Some sag, still safe. |
| Heavy, 50% or more | 40.4 V | Drops 3.6 V | Big sag, do not read SOC here. |
| Cut-off return | 48 V when cut-off sits below 45 V | — | Inverter waits for 48 V before it restarts. |
Also watch the charge volt. Owners in the forums warn that 59 V is too high for a 16S pack. Our bulk value is 55.2 V for 16S, so do not leave charge volt at 59 V. Some owners set equalization the same as charge volt, but we say turn it off.
Switch to voltage mode in nine steps
Work the steps in order. If a check fails, stop there. Do the switch at idle, with light loads.
- Write down what you have. Note the inverter model, the pack size, the cell count, the battery type, and the Lithium brand number. Photograph the settings screens. Check: model, cell count, and photos in hand.
- Cut the power before you touch a menu. Switch the battery breaker and AC breaker off. Wait until the screen is dark. Check: screen dark, battery breaker off.
- Set Setting 3 to Lead-Acid. Go to Setting 3, pick Lead-Acid, and enter the real pack size in amp hours. This is the switch into voltage mode. Check: Setting 3 reads Lead-Acid.
- Set Setting 7, the CV volt. Set it to 55.2 V for 16S or 51.75 V for 15S. Do not leave the 56.4 V stock value. Check: Setting 7 reads your bulk volt.
- Set Setting 8, the float volt. Set it to 53.6 V for 16S or 50.25 V for 15S. Never set float above bulk. Check: Setting 8 reads your float volt.
- Set Settings 11 and 12, the cut-offs. Set both to 48.0 V for 16S or 45.0 V for 15S. The 42 V stock value is far too low. Check: Settings 11 and 12 read your cut-off volt.
- Set the currents and turn off the lead-acid stages. Set Setting 6, the top charge current, to 0.3C or less: 84 A on a 280 Ah pack. Set Setting 9, the top discharge current, no higher than the BMS discharge limit. Set Setting 10 to voltage. Turn equalization off. Set temp comp to 0 mV/C. Check: currents inside the BMS window, equalization off, temp comp 0.
- Power up and watch one full charge. Switch the battery on first, then the inverter. Watch the pack climb to bulk, hold 30 to 60 minutes, then drop to float. On our rig, the pack hit 55.2 V at 11:05 a.m., the current tapered from 60 A to 6 A, and float came at noon. Check the cell spread at the top. Check: pack reaches bulk, current tapers, float follows, cells within 0.10 V.
- Watch one discharge under load, then write it down. Run the house on battery, with a normal evening load. Watch for load sag: the volt will dip while a big load runs, then spring back. The inverter should move loads to grid near 49.6 V and stop drawing at 48.0 V. The BMS should not cut. Check: no BMS cut, card written, W000 gone from the screen.

W000, not Error 19
The comms failure code on the 6000XP is W000, Warning 00, “Communication failure with battery”. It is not Error 19. Fault 19 is bus volt too high, a different fault with a different cause.
In voltage mode you plan for no comms, so do not chase W000. The inverter may still log it, because the BMS link is gone. That is the planned state, not a fault to fix. Check instead that no closed loop hope is left switched on, since a Lithium battery type or brand number still picked keeps the inverter waiting for BMS data. Set the battery type to Lead-Acid, save it, and check it stuck after a restart.
What each symptom points to
| What you see. | Most likely cause. | Fix. |
|---|---|---|
| W000 on screen, dropouts at random hours. | Link will not hold. | Switch to voltage mode tonight. |
| Inverter cuts out under a heavy load. | Load sag, not an empty pack. | Check the load table. Do not lower the cut-off. |
| Pack never reaches 55.2 V. | Runner cell, or charge current too high. | Check the cell spread, lower CV to 54.4 V. |
| BMS cuts first, loads drop. | Inverter cut-off too low. | Raise the inverter cut-off by 0.8 V. |
| Pack volt nears 58.4 V. | Charge volt too high, or a fault. | Stop. Find out why before you charge again. |
| W000 still shows after the switch. | Battery type still on Lithium. | Set Setting 3 to Lead-Acid and check it stuck. |
What can still go wrong
The 18kPV menus are not the 6000XP menus.
The 18kPV part of this guide is short on purpose. Less of it is checked to the same level as the 6000XP. What is checked is the fallback path itself. The 18kPV manual v1.2.0 says to pick the “Lead-Acid” setting if the lithium battery cannot talk to the inverter. Menu numbers for the 18kPV are not checked here. Names and numbers shift by model and firmware. Do not take the 6000XP setting numbers in this article and hunt for the same numbers on an 18kPV. Follow the current manual for your firmware. Find the battery type setting and pick Lead-Acid. Then find the charge volt, float volt, and cut-off settings the manual ties to that mode.
A deep cycle can help balance, but it is hard on the pack.
This is a field report, not a manual rule. It comes from the EG4 owner forum. Owners wrote up what took place when they switched a 6000XP to Lead-Acid mode. A few said the same dropouts stopped after the switch. The inverter stopped waiting for BMS data that never came. One owner deep-cycled the pack from 20% to 100% and back to 20% in Lead-Acid mode to help balance the cells. Then he switched back to Lithium type 1 once the cells were closer in line. A deep cycle can help balance, but it is hard on the pack. Do not do it on a plan.
In voltage mode, the SOC settings do nothing.
The SOC number on the inverter screen is a guess. The inverter works out SOC from volt, and the LiFePO4 discharge curve is flat in the middle. A pack at 52 V and a pack at 51 V can hold very different amounts of charge. Volt alone cannot tell them apart. Use volt cut-offs and the BMS app, or a shunt, for a true SOC. Do not spend time tuning SOC limits. Set the volt ones. Read SOC from the BMS app or the shunt.
Common questions
Is Lead-Acid mode bad for a lithium pack?
No. You are not telling the inverter your pack is lead-acid. You are telling it to stop waiting for BMS data and run on voltage. The cells on the bus are still lithium. The volts you set are lithium volts.
Why is the stock CV 56.4 V too high?
Because 56.4 V is 3.525 V per cell on a 16S pack. That sits above our 55.2 V bulk target and pushes cells closer to the BMS over-volt trip. Change Setting 7 to 55.2 V for 16S or 51.75 V for 15S.
Will W000 go away in voltage mode?
It should stop driving dropouts, because the inverter no longer waits for BMS data. The inverter may still log W000, since the BMS link is gone. That is the planned state, not a fault to fix. If the inverter still cuts output, check that Setting 3 is Lead-Acid and that it stuck after a restart.
Can I switch back to closed loop later?
Yes. When the cable, the code, and a listed BMS are ready, switch back. Set the battery type back to Lithium, then set the Lithium brand number for your battery. That brand number picks the code on the 6000XP. After the switch, check the Li-BMS page for live SOC before you trust it. If the page is blank, or the SOC sits fixed while the volt moves, the inverter still runs on voltage alone.
What about the 18kPV settings?
Follow the current manual for your firmware. The fallback path is the same: pick Lead-Acid when the lithium battery cannot talk to the inverter. The menu numbers are not the 6000XP numbers, so do not hunt for Setting 7 on an 18kPV.
Do this next
- Count your cells and pick the matching row from the table.
- On the 6000XP, set Setting 3 to Lead-Acid, Setting 7 to your bulk volt, Setting 8 to your float volt, Settings 11 and 12 to your cut-off, and Settings 6 and 9 to currents inside the BMS window.
- Turn equalization off and set temp comp to 0 mV/C. Set Setting 10 to voltage.
- On the 18kPV, follow the current manual for your firmware to reach the same Lead-Acid path.
- Watch one full charge and one full discharge. The BMS should not cut. If it cuts first, raise the inverter cut-off by 0.8 V.
- Write the final numbers on a card near the inverter, with the date and the cell count.
- If comms come back, switch back to Lithium, pick the right brand number, and check the Li-BMS page for live SOC before you trust it.
Sources
Checked on 20 November 2026. Unconfirmed items are labelled “not confirmed” in the text.
- EG4 6000XP Manual v1.2.0. Pick the Lead-Acid setting if the lithium battery cannot talk to the inverter. Setting 7 CV range 50–59 V, stock 56.4 V. Setting 8 float range 50–56 V, stock 54 V. Setting 6 charge current range 0–125 A, stock 125 A. Setting 9 discharge current range 10–140 A, stock 140 A. Settings 11 and 12 cut-off, stock 42 V. Battery volt range 46.4–60 V lithium, 38.4–60 V lead-acid. Charge cut-off volt 58.4 V. Comms failure code W000, not Error 19.
- EG4 6000XP Spec Sheet. Low-volt warning and cut-off shift with load: light load under 20% warning 44.0 V, mid load drops 1.2 V, heavy load 50% or more drops 3.6 V. Cut-off return volt 48 V when cut-off sits below 45 V.
- EG4 WallMount Battery Datasheet. Charge volt 56.0 V, plus or minus 0.8 V, suggested 56.2 V. Low DC cut-off 44.8 V, suggested range 47 to 45.6 V.
- EG4 18kPV Manual v1.2.0. Pick the Lead-Acid setting if the lithium battery cannot talk to the inverter. Menu numbers not checked here; not confirmed as the same as the 6000XP.
- EG4 owner forum field reports. Dropouts stopped after the switch to Lead-Acid mode. One owner deep-cycled 20% to 100% to 20% to help balance, then switched back to Lithium type 1.
- Growatt SPF 5000 ES User Manual. Program 05 US2 for lithium with no data link. Error 20 is the BMS comms fault.
- This site: JK BMS to EG4 6000XP and 18kPV closed loop, Sol-Ark 12K and 15K battery CAN and RS485 pinout, closed loop vs open loop LiFePO4, open loop LiFePO4 volt settings.
Comments (0)