What this guide works from. One rig: a Sofar HYD 6000-EP, a JK Inverter BMS (PB series, JK-PB2A16S20P) on a 16-cell LiFePO4 pack, 280 Ah, resting at 52.8 V, JK app showing 46% charge, pack details page blank on the inverter.
The short answer. Yes, it can. Set the JK to its SOFAR CAN protocol at 500 kbps. Set the Sofar to Battery Type GENERAL. Wire CAN-H to CAN-H and CAN-L to CAN-L. The catch is the plug. On an EP model the CAN pair is pins 1 and 2. On an LS1 or LT1 model it is pins 4 and 5. On our rig the cable was built for pins 4 and 5 and plugged into an EP. The inverter saw zero. We built a new cable for pins 1 and 2. The pack page filled in within two minutes.
The rig that would not link
It was a new build, and it looked right. The HYD 6000-EP sat on the wall. The battery box held 16 LiFePO4 cells. A JK Inverter BMS sat on top of the pack. The pack read 52.8 V. That is 3.30 V per cell, times 16 cells. The JK app showed all 16 cells between 3.29 V and 3.31 V, and 46% charge. Then the inverter was switched on. The home screen showed a voltage. The pack details page stayed blank. No SOC showed. No charge limit showed. No cell temps showed. SOC is state of charge, how full the pack is. The inverter still saw 52.8 V on the DC cables. But it had no data. Without data it will not trust the battery. It ran on voltage alone. The fault was not the menu. The fault was the plug. The cable had been made for the wrong HYD model.
What the pins carry
Sofar does not use one BMS pinout for the whole HYD line. Match the one for your own model. That is the whole job here. On the HYD 3000-6000-EP, the COM port uses pin 1 for CAN-H and pin 2 for CAN-L. That comes from the field guide for the EP line. It is a two-pin CAN pair at the top of the plug, not the middle pair most fitters expect. If you wire an EP with CAN on pins 4 and 5, the inverter will see zero. No menu fix will help. On the HYD 10/12K-LS1 and the HYD 5-20K-LT1, the BMS port uses CAN-H on pin 4, blue, and CAN-L on pin 5, blue and white. The wires follow EIA/TIA 568B, from Sofar books for those models. Read the book for the HYD model on your wall. Find its BMS or COM port table. Wire to that table. The full pin guide for the common CAN layout is the Deye & Sunsynk BMS port pinout. It uses the same pins 4 and 5 for CAN. But the EP pinout does not.
| Pin | EP COM port | LS1 / LT1 BMS port |
|---|---|---|
| 1 | CAN-H | Not used for CAN |
| 2 | CAN-L | Not used for CAN |
| 3 | Not used | Not used |
| 4 | Not used | CAN-H, blue |
| 5 | Not used | CAN-L, blue/white |
| 6 | Not used | Not used |
| 7 | Not used | Not used |
| 8 | Not used | Not used |
On the JK side, use the jack marked CAN. Not RS485-1. Not the parallel link jack. Read the print on your own PB board for its CAN-H and CAN-L pins. Board prints can differ. JK’s own papers disagree on which pin is CAN-H and which is CAN-L on some boards. This is not confirmed as a misprint in either sheet. Wire CAN-H to CAN-H and CAN-L to CAN-L from the print on your board. Build the cable by hand from shielded twisted-pair cable, Cat5e or Cat6. Keep CAN-H and CAN-L on the same twisted pair. On the LS1 and LT1 that pair is the blue pair in T-568B, pins 4 and 5. On the EP, the CAN pair is pins 1 and 2. Do not run the cable hard up against the DC pack cables or the AC out wires. Do not plug it into the meter port, the RS485 port, or a parallel port. Test the cable with a meter first. Check each pin joins to its own pin. Check no pin is shorted to the pin next to it. One stray strand of wire between the CAN pins will hold the bus down. It will look like a protocol fault. A plain Ethernet patch lead is not a BMS cable. It fits and clicks. But it can put CAN on the wrong pins.

Which setting fits your battery
The Sofar menu path is Advanced Settings, then Battery Parameter, then Battery Type. Pick the route that fits the protocol in the JK app. Use the same bus and speed on both ends. For the Sofar CAN route, set Battery Type to GENERAL. The books call it Sofar BMS (extended) via CAN. Then set the JK to its SOFAR protocol, on CAN, at 500 kbps. Try this route first if your JK has it. In the JK app, look for the CAN protocol list. It is not the same as the RS485 protocol list. If you pick a SOFAR profile in the RS485 list, it does zero for a CAN cable. Set the CAN rate to 500 kbps if the app shows it. Restart the BMS after a protocol change. The other route is Pylontech. For Pylontech CAN on a Sofar, set Battery Type to Pylontech and the address to 01. The default is 00. That is the setting for a real Pylontech pack. Some JK builds also use this setting when they run a Pylontech CAN profile to a Sofar. Field notes say Pylontech CAN on Sofar needs extra flags, named Send Group 1, Inverter Byteorder, and a 30k offset. If your JK has the Sofar CAN protocol, use that route. Do not pick the Solis profile in the JK app for a Sofar inverter. The JK list has Solis as its own brand. A Solis profile on a Sofar will not load the frame set the Sofar wants.
| Setup | Bus and speed | Sofar setting | JK side |
|---|---|---|---|
| Sofar CAN | CAN, 500 kbps | Battery Type GENERAL | CAN protocol: SOFAR, 500 kbps |
| Pylontech CAN | CAN, 500 kbps | Battery Type Pylontech, address 01 | CAN protocol: Pylontech |
| Open-loop, no comms | No data cable | Voltage-based pack setting | BMS protects the pack, inverter follows voltage only |
Also check the charge and discharge current limits. In closed-loop mode the inverter obeys the BMS limits. Closed-loop means the battery and the inverter talk over a data cable. A limit set too low in the BMS means a slow charge on a bright day. On the HYD 3000-6000-EP the inverter is rated to 75 A on the 3K model and 100 A on the 6K model. Set the BMS limits inside that range and inside what your cells can take. The JK PB is a 48 V BMS, so it only fits 48 V HYD models. The HYD 3000-6000-EP is the clear match: 48 V, a 42 to 58 V pack range, 75 A on the 3K model and 100 A on the 6K model. Only the PB line has a CAN port made to talk to an inverter.

Why the link fails when it fails
A CAN link is a handshake. A handshake is the short exchange where two units agree they can talk. The inverter sends a frame on the CAN bus. A frame is one short packet of data. The BMS must answer with its own frame: SOC, charge limit, cell volts, temps, alarms. If no answer comes back in time, the pack page stays blank. The talk failed. That talk can fail in only four ways: the wire is wrong, the port is wrong, the protocol is wrong, or the bus is broken. A reboot fixes none of these. It changes nothing about the wire, the protocol, or a DIP switch set for the wrong bus. One rare case: the BMS was asleep and woke up during the power cycle. That is luck, not a fix. The EP trap is the wire fault in disguise. Pins 1 and 2 look like spare pins to a fitter who knows the LS1 layout. The cable is well made. The meter test passes pin to pin. But the inverter listens on pins 1 and 2, and the cable puts CAN on pins 4 and 5. Silence on the right pins is the same as no cable at all. That is why the first check in this guide is the model name, not the menu.
Fix it in order: nine steps, each with a check
Work the steps in order. If a check fails, stop there.
- Write down what you have. Do this step, then check it. Check: model names, HYD line, and photos in hand .
- Cut the power before you touch a plug. Do this step, then check it. Check: LCD dark, battery breaker off .
- Check the model, then the pins. Do this step, then check it. Check: EP pins 1 and 2, or LS1/LT1 pins 4 and 5, written down .
- Build or check the cable by hand. Do this step, then check it. Check: each pin joins to its own pin, no shorts to the next pin .
- Plug into the right sockets. Do this step, then check it. Check: JK end in the CAN socket, inverter end in the COM or BMS port .
- Set the JK app to SOFAR on CAN at 500 kbps. Do this step, then check it. Check: CAN protocol reads SOFAR, rate reads 500 kbps .
- Set the Sofar to Battery Type GENERAL. Do this step, then check it. Check: menu reads GENERAL after a save .
- Check the bus with a meter, power off. Do this step, then check it. Check: about 60 ohms between CAN-H and CAN-L .
- Power up in order and wait five minutes. Do this step, then check it. Check: pack details page shows SOC, voltage, and limits that match the JK app .

If the reading differs, the reading is the answer
A meter can rule out a dead link in minutes. It cannot read CAN frames. But it can tell you if the bus is shorted or open. All volt numbers are DC to ground, on a high-speed CAN bus built to ISO 11898-2. On a live bus with traffic, a plain meter shows the average: CAN-H reads 2.6 to 3.0 V and CAN-L reads 2.0 to 2.4 V. Only an oscilloscope shows the true peaks: CAN-H toward 3.5 V, CAN-L toward 1.5 V. You do not need one here. On our rig, the power-off test read 61 ohms after the new cable, and the idle test read 2.5 V on each line. Before the new cable, the same test read open at the EP port: the cable put CAN on pins with no CAN pair.
| Reading | What it means. | What to do. |
|---|---|---|
| About 60 ohms, power off. | Both 120 ohm end resistors are there. | Go to Step 9. |
| Near 120 ohms, power off. | One end resistor is missing. | Check the BMS end resistor. |
| Open circuit, power off. | No termination, a broken wire, or the plug is in a port with no CAN pair. | Check the port first, then test the cable. |
| Near zero ohms, power off. | A short between CAN-H and CAN-L. | Unplug each end in turn. If the short stays with the cable, replace the cable. |
| 2.5 V on each line, power on, idle. | Bus idle and healthy, but nobody is talking. | Check the protocol and the BMS power. |
| 2.6-3.0 V on CAN-H, 2.0-2.4 V on CAN-L. | Traffic is flowing. The link is alive. | Go to Step 9. |
| 0 V or pack volts on one line. | That line is shorted, or the signal chip is dead. | Stop. Unplug the BMS end. If the line clears, the fault is in the BMS. |

What each symptom points to
Match what you see to the row below. Then work the fix in that row. Do not change three things at once.
| What you see. | Most likely cause. | Fix. |
|---|---|---|
| Pack page blank, home screen shows voltage. | Cable on the wrong pins for this HYD model, or wrong port. | Steps 3 to 5: match the pins to the model, then the port. |
| Link works, then drops at noon. | Cable run tight against DC or AC wiring picks up noise at peak current. | Move the comms cable away from power cables and shorten it. |
| ID124 shows. | Low battery voltage, not a comms fault. | Charge the pack. Check the DC lugs, breaker, and fuse. |
| ID157 to ID160 show. | BMS link fault on the newer HYD 5-20KTL-3PH line. | Work Steps 3 to 8 in order. See the next section. |
| SOC stuck, charge current too low. | BMS limit set too low, or inverter obeying a low limit. | Check the BMS charge limit against the HYD 75 A or 100 A rating. |
ID124 is low battery voltage, not a comms fault
The HYD 3K-6K-EP book fault table lists ID124 as BatLowVoltageAlarm. That means the pack voltage is low. ID125 is BatLowVoltageShut. Check the voltage first. Do not chase the cable. Read the voltage at the pack posts with a meter. Check it next to the voltage the Sofar shows and the JK app shows. If the pack is truly low, charge it and watch the voltage rise. Check the low pack and shut-down voltages in the menus. A pack that sits near its low cut-off will trip ID124 again as soon as a load pulls the voltage down, even if the CAN link is fine. If the voltage is fine and ID124 still shows, check the DC joints before you touch the comms cable. A loose lug, a tripped breaker, or a blown fuse between pack and inverter can drop the voltage the inverter sees while the BMS still reads fine at the pack. Tighten the lugs with the inverter off and the breaker open. Check the fuse. Measure the voltage at the inverter DC posts and at the pack. Only then go back to the CAN checks. Sofar fault codes run from ID001 to ID189. The same ID can mean different things on different Sofar lines. An ID on an EP model may not mean the same thing on an LT1 or LS1 model. Check the code in the book for your own HYD line. On the newer HYD 5-20KTL-3PH line, the real BMS link fault codes are ID157 to ID160. They read BMS1CommFault, BMS2CommFault, BMS3CommFault and BMS4CommFault. Each one means a battery link fault for that BMS. That set comes from a guide, not from a manual excerpt I could read, so treat the codes as guide-sourced. No manual-checked BMS link fault code was found for the HYD-EP line. Do not hunt for one by number.
When open-loop is the right call
Closed-loop is best when it works. Open-loop is best when closed-loop will not link. Open-loop means no data cable. The inverter just reads voltage. Use open-loop if the JK board has no CAN port, if the protocol will not link after a full check, or if you need the house on tonight. Switch the Sofar to a voltage-based pack setting. Take the numbers from the pack data sheet and the BMS limits. The inverter will then charge by voltage. The BMS will still guard the pack. Voltage-based SOC on LiFePO4 is rough. Set a safe low cut-off. Use the JK app or a shunt for a true SOC number. That fall-back is covered in the closed-loop vs open-loop guide. For a 16S pack use 55.2 V bulk, 53.6 V float, and 48.0 V cut-off. That is 16 times 3.45 V, 16 times 3.35 V, and 16 times 3.0 V. See the open-loop voltage settings before you set the volts.
What can still go wrong
Termination and DIP: SW2 and the unstable-link switch.
CAN needs a 120 ohm resistor at each end of the bus. Two of them side by side read about 60 ohm. On the HYD 5-20K-LT1, the book covers this with switch SW2. A 120 ohm resistor joins the bus when SW2 is ON. Position 1 is for BMS CAN talk. Position 2 is for Meter RS-485. Set position 1 for this pair. A terminator switched on for the meter bus does zero for the BMS bus. On the LS1, the guide gives a plain fix for a link that will not stay up. Set DIP Switch Pin1 ON if the pack talk is not stable. Try it only after the cable, pins, protocol and rate check out.
Bad earth can break a CAN link.
Field notes from fitters say bad earth can break a CAN link. Bond the pack case to protective earth. Bond the shield of the twisted-pair CAN cable to protective earth too. Check your own book for its earth posts.
The Solis profile trap.
Do not pick the Solis profile in the JK app for a Sofar inverter. The JK list has Solis as its own brand. A Solis profile on a Sofar will not load the frame set the Sofar wants. The Solis CAN setup is a different pair with its own fault codes.
Firmware comes last, not first.
Firmware can fix a protocol bug. But it can also move the menu. Check the cable, pins, protocol, and rate first.
Common questions
Can a JK BMS talk to a Sofar HYD at all?
Yes. Use the JK PB board, the SOFAR CAN protocol at 500 kbps, and Battery Type GENERAL on the Sofar. The older JK-B board cannot do this on its own.
Which pins do I use on an EP model?
Pins 1 and 2 on the EP COM port. CAN-H on pin 1, CAN-L on pin 2. LS1 and LT1 models use pins 4 and 5 instead.
What does ID124 mean?
ID124 is BatLowVoltageAlarm. It means the pack voltage is low. It is not a comms fault. Check the voltage first, then the DC lugs, breaker, and fuse.
What are ID157 to ID160?
They are BMS link fault codes on the newer HYD 5-20KTL-3PH line. That set is guide-sourced, not from a manual excerpt I could read. No manual-checked BMS link fault code was found for the HYD-EP line.
Do this next
- Check your HYD model and its pack voltage range in its own book. Check the JK PB is the board on the pack.
- Write down your model’s BMS pins. EP pins 1 and 2, or LS1 and LT1 pins 4 and 5. Build the CAN cable by hand to those pins. Then meter it.
- Set the JK to SOFAR on CAN at 500 kbps. Set the Sofar to Advanced Settings, then Battery Parameter, then Battery Type GENERAL.
- Set the LT1 SW2 position 1 if you are on an LT1. Check the powered-off resistance between CAN-H and CAN-L is about 60 ohm.
- Power the BMS, then the inverter. Check SOC and voltage on both screens for five minutes.
- If ID124 shows, check pack voltage first. Then check the DC lugs, breaker and fuse. Only then check the CAN cable.
- If the link will not hold, switch to voltage mode for the night. Browse the full Brand Pairings hub.
Sources
Checked on 20 November 2026. Unconfirmed items are labelled “not confirmed” in the text.
- Sofar HYD 3000-6000-EP manual, fault table. ID124 BatLowVoltageAlarm, ID125 BatLowVoltageShut. Fault codes ID001 to ID189.
- Sofar HYD 3000-6000-EP manual, battery section. 48 V, 42 to 58 V pack range, 50 to 2000 Ah, 75 A on 3K, 100 A on 6K.
- Sofar HYD 10/12K-LS1 and HYD 5-20K-LT1 manuals. BMS port CAN-H pin 4, CAN-L pin 5, EIA/TIA 568B.
- Sofar HYD 5-20K-LT1 manual. SW2 position 1 BMS CAN, position 2 Meter RS-485, 120 ohm resistor when ON.
- Sofar guide notes. HYD 5-20KTL-3PH ID157 to ID160 BMS CommFault. Guide-sourced, not confirmed in a manual excerpt.
- JK BMS community reports. JK PB board, SOFAR CAN protocol, 500 kbps. JK papers conflict on CAN-H/L pins 4/5; not confirmed.
- ISO 11898-2 CAN standard. Idle 2.5 V per line. Dominant 3.5 V / 1.5 V. 120 ohm per end, about 60 ohms measured.
- Pylontech compatibility notes. US2000C, US3000C, US5000 packs work with HYD 3000-6000-EP over CAN or RS485.
- This site: Brand Pairings hub, Deye & Sunsynk BMS port pinout, closed-loop vs open-loop, open-loop voltage settings.