Closed-Loop vs. Open-Loop Tuning ✓ BENCH VERIFIED UPDATED NOVEMBER 21, 2026 15 MIN READ 3,104 WORDS

Growatt SPF 5000 ES: Should You Switch From Li to USE Mode?

Farhan Ahamed
Farhan Ahamed Published November 19, 2026 · 15 min read
0 COMMENTS
Growatt SPF 5000 ES: Should You Switch From Li to USE Mode?
IN THIS GUIDE · QUICK JUMP KEY SECTIONS
01 · KEY SECTION Jump ↓

The link that would not stay up

It was a new build, and it looked right. The SPF 5000 ES sat…

02 · KEY SECTION Jump ↓

What actually changes when you leave Li mode

First, Programs 12, 13, and 21 stop showing SOC percent from the BMS and…

03 · KEY SECTION Jump ↓

Programs 19, 20, and 21: the numbers for 16S and 15S

When Program 05 is USE or US2, the charge volt and low DC cut-off…

04 · KEY SECTION Jump ↓

Why Li mode locks you out when the link fails

In Li mode the inverter trusts the BMS, not the volts. That trust is…

05 · KEY SECTION Jump ↓

The switch in nine steps

Work the steps in order. If a check fails, stop there. Do the switch…

06 · KEY SECTION Jump ↓

If the reading differs, the reading is the answer

Step-by-step field verification & diagnostic reference inside this section.

07 · KEY SECTION Jump ↓

What each symptom points to

Step-by-step field verification & diagnostic reference inside this section.

08 · KEY SECTION Jump ↓

USE or US2: which one?

Program 05 holds the battery type. The options are AGM, Flooded, Lithium, USE, and…

09 · KEY SECTION Jump ↓

What can still go wrong

Step-by-step field verification & diagnostic reference inside this section.

10 · KEY SECTION Jump ↓

Common questions

Step-by-step field verification & diagnostic reference inside this section.

11 · KEY SECTION Jump ↓

Do this next

Step-by-step field verification & diagnostic reference inside this section.

12 · KEY SECTION Jump ↓

Sources

Checked on 20 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

What this guide works from. One rig: a Growatt SPF 5000 ES, a JK Inverter BMS on a 16-cell LiFePO4 pack, 280 Ah, resting at 52.8 V, JK app showing 47% charge, Error 20 on boot that keeps coming back.

The short answer. Yes, you can switch a Growatt SPF 5000 ES from closed loop Li mode to USE mode. The switch itself takes about two minutes. Closed loop means the inverter and the BMS talk and work as one system. The BMS is the battery’s guard board. USE mode means the inverter charges by voltage alone, with no data link. Set Program 05 to USE. Set Program 19 bulk to 55.2 V. Set Program 20 float to 53.6 V. Set Program 21 low DC cut-off to 48.0 V for a 16S LiFePO4 pack. Turn equalization off. Set temp comp to 0 mV/C. The inverter will then charge by voltage alone. The BMS will still guard the pack. The only thing you lose is the data link. No BMS state of charge, or SOC, shows on the screen. No BMS charge limits apply. Write down your Li settings first. Check one full charge and discharge.

The link that would not stay up

It was a new build, and it looked right. The SPF 5000 ES sat on the wall, and the battery box held 16 LiFePO4 cells. A JK Inverter BMS sat on top of the pack. The pack read 52.8 V: 3.30 V per cell, times 16 cells. The JK app showed all 16 cells between 3.29 V and 3.31 V, and 47% charge. Then the inverter was switched on, and Error 20 showed within seconds. The small Li icon flashed on and off, and no state of charge showed. The inverter still saw 52.8 V on the DC cables, but it had no data: no SOC, no charge limit, no cell temps.

We worked the full Error 20 checklist first. The plug was in the CAN port on the BMS and the BMS port on the inverter. Program 05 read LI and Program 36 read L52. The bus read about 60 ohms with power off and 2.5 V per line with power on. The link came up, then dropped again by noon. Twice. It was 7 p.m., the sun was gone, and the house needed power. So we switched to USE mode that night and kept the link fault for daylight. The next morning told us the switch worked. Solar came up at 7 a.m. At 10:40 a.m. the pack hit 55.2 V, and the charge current tapered from 60 A down to 8 A. At 11:30 a.m. the inverter dropped to float at 53.6 V. The app showed all 16 cells between 3.44 V and 3.46 V, and 100% charge. That evening the house ran on battery. At 9:15 p.m. the pack fell to 49.6 V and the inverter moved the loads to grid. The BMS app showed 22% charge at that point. The inverter screen showed 31%. The screen was guessing from volts. The app was counting amps. We trusted the app.

What actually changes when you leave Li mode

First, Programs 12, 13, and 21 stop showing SOC percent from the BMS and go back to showing volts.

Second, the max charge current becomes yours to set. In Li mode the inverter follows the BMS limit. In USE mode you set it yourself in Program 02, with a top value of 100 A. Set it wrong and only the BMS stops an over-current charge. Keep it at 0.3C or below for LiFePO4: 84 A on a 280 Ah pack, 30 A on a 100 Ah pack.

Third, Program 36 picks the code: L01 to L50 for RS485, L51 to L99 for CAN. Pylontech CAN is L52 and Pylontech RS485 is L04, so keep the code in your notes for the switch back.

SettingLi mode (closed loop)USE mode (open loop)
Charge targetSet by the BMS.Set by you in Programs 19 and 20.
Low cut-offPercent, set by the BMS.Volts, set by you in Program 21.
Charge current limitSet by the BMS, user cannot change it.Set by you, 0.3C or below.
SOC on screenLive BMS SOC.Volt guess, rough.
Comms failureInverter cuts output (Error 20).No comms to fail.
BMS guardActive, and sent to the inverter.Active, but not sent.

Closed loop is better when it works. The BMS tells the inverter the real state of charge, current limit, and alarm flags, and the inverter follows them. The most common reason to leave it is a comms fault that will not clear. Growatt Error 20 is the BMS comms fault on the SPF series. It cuts output when the inverter is in Li mode and the messages stop arriving. If you have worked through the cable, the pins, the code, and the power cycle, and Error 20 keeps coming back, USE mode gets the house running again tonight. The Growatt Error 20 fix has the full checklist if you want to keep fighting for the link first. The second reason is a BMS with no code the SPF 5000 ES understands. The manual says the Lithium setting in Program 05 is only fit when the battery talks with the BMS. If your BMS speaks a code the inverter does not list, or has no CAN or RS485 port, there is nothing to close the loop with.

Programs 19, 20, and 21: the numbers for 16S and 15S

When Program 05 is USE or US2, the charge volt and low DC cut-off are set in Programs 19, 20, and 21. Manual ranges are wide. Program 19 bulk runs 48 V to 58.4 V. Program 20 float runs 48 V to 58.4 V. Program 21 low cut-off runs 40 V to 48 V. The right numbers come from cell count and chemistry.

For 16S LiFePO4, 51.2 V nominal: Program 19 bulk 55.2 V (3.45 V per cell). Program 20 float 53.6 V (3.35 V per cell). Program 21 low cut-off 48.0 V (3.0 V per cell). Bulk at 3.45 V charges the pack to full. It does not push cells into the knee, where volt shoots up.

For 15S LiFePO4, 48 V nominal: Program 19 bulk 51.75 V. Program 20 float 50.25 V. Program 21 cut-off 45.0 V. Do not use the 16S numbers on a 15S pack. 55.2 V bulk is 3.68 V per cell. That is past the 3.65 V guard point of most BMS boards. The BMS will trip the charge every time the pack nears full. The reverse leaves a 16S pack half charged.

Program 12, back to utility: 49.6 V on 16S, 46.5 V on 15S. Program 13, back to battery: 52.8 V on 16S, 49.5 V on 15S. Keep about 3 V between them on a 16S pack. If the gap is too small, the inverter chatters between grid and battery every time a cloud passes.

ProgramWhat it sets16S pack (51.2 V nominal)15S pack (48.0 V nominal)
19 BulkTop charge volt.55.2 V (3.45 V per cell).51.75 V (3.45 V per cell).
20 FloatHold volt after full.53.6 V (3.35 V per cell).50.25 V (3.35 V per cell).
21 Low cut-offLow DC cut-off.48.0 V (3.00 V per cell).45.0 V (3.00 V per cell).
12 Back to utilityMove loads to grid.49.6 V (3.10 V per cell).46.5 V (3.10 V per cell).
13 Back to batteryMove loads back to pack.52.8 V (3.30 V per cell).49.5 V (3.30 V per cell).
BMS under-volt cutLast guard, BMS trips.44.8–46.4 V.42.0–43.5 V.

Why Li mode locks you out when the link fails

In Li mode the inverter trusts the BMS, not the volts. That trust is the whole point of closed loop, and it is also the trap. The inverter takes its SOC, its charge limit, and its cut-off points from the BMS data. When the data stops, the inverter has no safe numbers to fall back on. So it cuts output and shows Error 20. It would rather cut the house than charge a pack it cannot see.

In Li mode the inverter also locks the max charge current. You cannot change it in the menus. The BMS sets it, and the inverter follows. The low cut-off and restart points switch to percent. The stock cut-off is 20%. That percent comes from the BMS SOC, so it means nothing once the link is gone. USE mode hands all of that back to you: the volts, the current, and the cut-offs. The price is that you must set them right, because no BMS data will catch a wrong number for you. The BMS still guards the pack, but it guards by cutting power, not by asking the inverter to slow down.

The same trust rule explains Warning 04. Warning 04 means low battery. The SPF 3500 ES manual says it is often caused by a link fault on lithium: fix the link fault first. The inverter cannot read the BMS, so it cannot trust the SOC. Do not clear Warning 04 by raising a volt setting. Charge the battery first, then fix the data link.

The switch in nine steps

Work the steps in order. If a check fails, stop there. Do the switch at idle, with light loads.

  1. Write down the Li settings. Note Program 05 and Program 36 exactly as they are. If Program 05 is LI, note the Program 36 code: L52 for Pylontech CAN, L04 for RS485, or your build’s code. Write down Programs 12, 13, and 21, plus the charge current. Photograph each screen. Check: Program 05, Program 36, and cut-offs in hand.
  2. Cut the power before you touch a menu. Switch the battery breaker, DC isolator, and AC breaker off. Wait until the LCD is dark. Check: LCD dark, battery breaker off.
  3. Set Program 05 to USE. Hold ENTER for three seconds to enter settings. Step to Program 05 and pick USE. Press ENTER to confirm, then step out. A quick tap does nothing. Check: Program 05 reads USE.
  4. Set Program 19, the bulk volt. For a 16S pack, set it to 55.2 V. For a 15S pack, set it to 51.75 V. If Program 05 is US2, set Program 20 to the same volt. Check: Program 19 reads your bulk volt.
  5. Set Program 20, the float volt. For a 16S pack, set it to 53.6 V. For a 15S pack, set it to 50.25 V. Never set float above bulk. Check: Program 20 reads your float volt.
  6. Set Programs 21, 12, and 13. Set Program 21, the low DC cut-off, to 48.0 V for 16S or 45.0 V for 15S. Set Program 12, back to utility, to 49.6 V for 16S or 46.5 V for 15S. Set Program 13, back to battery, to 52.8 V for 16S or 49.5 V for 15S. Check: Program 21 reads your cut-off volt, and Program 12 sits 1.6 V above it.
  7. Set the current and turn off the lead-acid stages. Set Program 02, the max charge current, to 0.3C or below: 84 A on a 280 Ah pack, 30 A on a 100 Ah pack. Turn equalization off. Set temp comp to 0 mV/C. Check: current at or below 0.3C, equalization off, temp comp 0.
  8. Power up and watch one full charge. Switch the battery on first, then the inverter. Watch the pack climb to bulk, hold 30 to 60 minutes, then drop to float. On our rig, the pack hit 55.2 V at 10:40 a.m., the current tapered from 60 A to 8 A, and float came at 11:30 a.m. Open the BMS app and watch the cells. The highest and lowest should stay within about 0.05 V of each other. Check: pack reaches bulk, current tapers, float follows, cells within 0.10 V.
  9. Watch one discharge, then write it down. Run the house on battery until the pack falls toward 48.0 V on 16S. The inverter should cut off at Program 21 and switch to grid. A cut-off a volt early usually means volt sag under load. Do not lower Program 21 to chase the last amp hour. 48.0 V is already 3.0 V per cell, and lower buys almost no energy. Check: grid switch at 49.6 V, no BMS cut, card written.

If the reading differs, the reading is the answer

ReadingWhat it means.What to do.
Li icon solid, SOC matches the BMS app.Link alive, closed loop.Stay in Li mode.
Li icon flashes, no SOC, Error 20.Link dead.Fix the link, or switch to USE tonight.
Pack hits 55.2 V, current tapers to near zero.Pack full, balancer working.Let it drop to float.
One cell runs toward 3.6 V, rest sit at 3.4 V.Pack out of balance.Lower bulk to 54.4 V. No inverter setting fixes balance.
Inverter cuts a volt early on discharge.Volt sag under load.Do not lower Program 21. Check the load.
BMS cuts before the inverter cut-off.Inverter cut-off too low.Raise Program 21 by 0.8 V.

What each symptom points to

What you see.Most likely cause.Fix.
Error 20 on boot, flashing Li icon, no SOC.Link fault: cable, port, or code.Fix the link, or switch to USE tonight.
Error 20 clears, then comes back at noon.Comms cable tight against DC or AC wiring picks up noise.Move the cable away from power cables.
Error 20 plus Warning 04.Low battery, and the inverter cannot read the BMS.Charge first if you can, then fix the link.
Inverter cuts at night, screen read 60%.Volt SOC lied under load.Use the BMS app for SOC.
BMS cuts first, loads drop.Program 21 too low.Raise Program 21 by 0.8 V.
Pack never reaches 55.2 V.Runner cell, or charge current too high.Check the cell spread, lower bulk to 54.4 V.

USE or US2: which one?

Program 05 holds the battery type. The options are AGM, Flooded, Lithium, USE, and US2. US2 is User-Defined 2. It is the manual’s pick for a lithium battery without BMS comms. USE is User-Defined. It is the setting most installers use for a 16S pack. With USE, Programs 19 and 20 can hold different values: bulk and a lower float. Pick USE for a bulk of 55.2 V and a float of 53.6 V on a 16S pack. Pick US2 to stop charging dead at one volt. Set the same volt in Programs 19 and 20. Growatt’s own FAQ gives the same fallback. If your battery is not on the Growatt list, set Program 05 to US2 and run without BMS data. The FAQ notes a current limit under 30 A for a single battery. Check your battery datasheet first.

What can still go wrong

Setting Program 21 too low when the house kept cutting out.

A 44 V floor on 16S is 2.75 V per cell, and the BMS trips on cell under-volt first. The house still cuts out, just later and harder. Fix the load or the cable before lowering the floor.

Forgetting the charge current.

In Li mode the BMS held the current down. In USE mode the inverter pushes its own max unless you set it in Program 02, the day you switch. A 280 Ah pack at 100 A is 0.36C. It will charge, but it will push the high cell up fast and leave less time for the balancer.

Trusting the inverter SOC display at night.

Volt-based SOC can read 60% when the pack is at 30%, and the house cuts out at 2 a.m. Use the BMS app until you have a shunt. A Victron SmartShunt sits on the battery negative wire and counts current in both directions. It gives a true SOC number when the inverter screen cannot.

Switching modes mid-charge.

Do not switch modes in the middle of a charge cycle if you can avoid it. Switch at idle, with light loads, and watch the first charge and discharge after the switch.

Common questions

Will USE mode hurt my lithium pack?

No, if the volts are right. The BMS still guards every cell. It cuts charge on a high cell and cuts discharge on a low cell. What you lose is early warning: the inverter cannot slow down before the BMS cuts. Keep the cut-off ladder wide so the inverter acts first.

What is the difference between USE and US2?

USE lets Programs 19 and 20 hold different values: bulk 55.2 V and float 53.6 V on a 16S pack. US2 sets Programs 19 and 20 to the same full-charge volt, so charging stops dead at one volt. US2 is the manual’s pick for lithium with no data link. Most installers use USE for a 16S pack.

Can I switch back to Li mode later?

Yes. Hold ENTER for three seconds, set Program 05 back to LI, then re-enter the Program 36 code: L52 for Pylontech CAN, L04 for RS485, or your build’s code. Save, power-cycle the BMS first, then the inverter, and wait two minutes. The inverter should show a live BMS state of charge. If it shows Error 20, the link is still broken. See the JK BMS to Growatt SPF 5000 ES setup for the CAN wiring and L52.

Why does the SOC on the screen lie in USE mode?

Because the inverter estimates SOC from volt, and the LiFePO4 curve is almost flat between 20% and 80%. A pack at 60% can read like 30% under load and like 90% under charge. Use the BMS app or a shunt for a true SOC number.

My pack is 15S. Can I use the 16S numbers?

No. Do not use the 16S numbers on a 15S pack: 55.2 V bulk is 3.68 V per cell, past the 3.65 V guard point of most BMS boards, so the BMS will trip the charge every time the pack nears full. Use 51.75 V bulk, 50.25 V float, and 45.0 V cut-off for 15S.

Do this next

  1. Write down Program 05 and Program 36, and photograph each screen.
  2. Switch at idle with light loads: hold ENTER for three seconds, set Program 05 to USE, and confirm.
  3. Set Program 19 to 55.2 V, Program 20 to 53.6 V, and Program 21 to 48.0 V for 16S, or 51.75 V, 50.25 V, and 45.0 V for 15S.
  4. Set the back-to points to 49.6 V and 52.8 V on 16S, or 46.5 V and 49.5 V on 15S.
  5. Turn equalization off, set temp comp to 0 mV/C, and set the charge current to 0.3C or below.
  6. Watch one full charge and one full discharge, and use the BMS app for SOC.
  7. If the numbers hold for a week, the switch is done. If you fix the comms link later, switch back with tonight’s notes: Program 05 to LI, Program 36 to L52 or L04, power-cycle the BMS first, and wait two minutes.

Sources

Checked on 20 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

QUESTIONS ANSWERED

Operator Questions Answered (Playbook FAQ)

Switch off the battery rack breaker, DC isolator, and AC input before handling RJ45 plugs on Hybrid Inverter LiFePO4 BMS. Powered down, measure DC resistance across Pins 4 (CAN-H) and 5 (CAN-L)—a healthy terminated bus reads ~60Ω (two 120Ω resistors in parallel), while 120Ω indicates one missing end resistor.

Farhan Ahamed
WRITTEN & AUDITED BY

Farhan Ahamed

Founder & Lead Protocol Architect • BMSBridge.online

Hardware diagnostics engineer specializing in 500 kbps CAN-Bus telemetry (0x351–0x35E), RJ45 VE.Can crossovers, and cell-safe 15S/16S LiFePO4 battery interoperability.