What this guide works from. One rig: a Deye 8K hybrid inverter, two Pylontech US3000C packs, and one DIY 16S pack with a JK BMS. Packs A and B are US3000C, 74 Ah, 3.552 kWh, 15 cells each. Pack C is the DIY pack, 280 Ah, 14.336 kWh, 16 cells. Total: 428 Ah and 21.44 kWh. The Deye runs Lithium Mode 00 on CAN, and the bridge is YamBMS on an ESP32.
The short answer. You cannot plug three BMS packs into one inverter port. The port expects one battery that speaks once per second. So you put a bridge in the middle. It reads all three packs, adds up their amp-hours and charge limits, and sends one set of CAN frames to the inverter. On our rig the fix was a YamBMS node. The inverter now sees one 428 Ah pack at 57% charge and a 174 A charge limit, instead of one 74 Ah pack at 62%.
The rig that hit the wall
The house had two Pylontech packs first, joined by the link chain, with the master pack talking to the Deye. Then the owner built a third pack: a DIY 16S pack with 280 Ah of EVE cells and a JK BMS. It held four times the energy of the two Pylontech packs put together, but it had no link port and could not join the chain.
At first the owner wired all three packs to one busbar and left the Deye talking to the Pylontech master only. The inverter saw 74 Ah, a 37 A charge limit, and 62% charge. Pack A filled up fast and cut the charge at 53.5 V, while pack C sat at 55% charge, holding most of the energy in the house.
The owner then tried the wrong fix: a second CAN cable from the JK pack to the same port. Two talkers sent two sets of frames with the same CAN IDs. The charge on the screen jumped between 62% and 55%, and the limit jumped between 37 A and 100 A. One port takes one battery. Three packs need one voice.
Why one port cannot hear three packs
A BMS is the board that guards a pack. It watches cell volts, temps, and current, and tells the inverter how much charge the pack can take. On a Pylontech CAN link, that talk is a set of short frames sent once per second at 500 kbps.

Frame 0x351 carries the charge volt limit and the charge and discharge current limits. Frame 0x355 carries SOC and state of health. Frame 0x356 carries pack volts, current, and temp. Frame 0x35E carries the maker name, “PYLON”. The inverter reads these frames and obeys them.
So two packs that both send frame 0x351 will fight. Each one overwrites the other, and the inverter sees a charge limit that flips each second. It cannot add them up. The same clash hits frame 0x355, so the SOC flips too.
The fix is a bridge between the packs and the inverter. It reads each pack on its own link: pack A on the Pylontech chain, pack C on RS485 from the JK BMS. Then it does the maths and sends one clean set of frames. The inverter hears one battery.
The three routes to one virtual battery
Three ways make three packs look like one battery.

Route 1 is native stacking, for packs of one brand and range. Pylontech packs link with RJ45 cables, and the pack with an empty Link Port 0 becomes the master. Up to 16 packs can sit in one group. Our rig fails this route: the JK pack has no Pylontech link port. The same master rules fit a Fox ESS stack; see the same-day Pylontech Fox ESS setup. Full stacking steps are in the Pylontech Deye DIP guide.
Route 2 is a CAN bridge. YamBMS runs on an ESP32 and merges mixed brands: JK, JBD, Seplos, PACE, BASEN, DEYE, and Ecoworthy. It sends PYLON, SMA, Victron, or LuxPower talk to the inverter over CAN or RS485. It is the route this guide builds. Install steps are in the YamBMS build guide, not repeated here.
Route 3 is Venus OS with dbus-serialbattery, for a Victron rig with a Cerbo GX. The driver reads each BMS over serial or Bluetooth and puts it on the Venus OS bus. Each pack shows as its own battery on the GX screen, and the GX adds up the amps for the system view. DVCC, the Victron charge control, then hands the limits to the chargers. See the dbus-serialbattery install and the Daly2MQTT driver guide.
| Route | Fits this rig | What it merges | Cost and skill | Main limit |
|---|---|---|---|---|
| 1. Native stacking | No, JK cannot join | One brand only | No extra box | One brand, one range |
| 2. YamBMS bridge | Yes, our pick | Mixed brands, 3 BLE or UART packs per node | ESP32 board | You build and test it |
| 3. Venus OS + dbus-serialbattery | Yes, if Victron | Serial and Bluetooth packs | Cerbo GX | Needs a GX device |
How the bridge adds the numbers
The bridge adds amp-hours, works out one SOC, adds the charge and discharge limits, and picks the lowest and highest cell volt.
Start with amp-hours: 74 + 74 + 280 = 428 Ah. Energy adds the same way: 3.552 + 3.552 + 14.336 = 21.44 kWh. The inverter now plans against 428 Ah, not 74 Ah.
SOC is not a plain average. It is weighted by amp-hours: 74 x 62 = 4,588 for pack A, 74 x 58 = 4,292 for pack B, and 280 x 55 = 15,400 for pack C. Add them: 24,280. Divide by 428 Ah: 56.7%. The bridge sends 57%. Stored energy now is 12.2 kWh, and about 10.0 kWh is left down to a 10% floor.
Charge volts are not added. The lowest full-charge volt wins. Packs A and B are 15S, and their manual gives 52.5 V to 53.5 V for charge. Pack C is 16S and wants 55.2 V at 3.45 V per cell. The bridge must send 53.5 V, or the Pylontech packs would hit over-volt protection. So the 16S pack never quite fills: at 53.5 V it sits at 3.34 V per cell.
Charge current has three caps, and the bridge takes the lowest. First, the user ceiling: 37 + 37 + 100 = 174 A. Second, the over-current sum times 0.9: (90 + 90 + 200) x 0.9 = 342 A. Third, the C-rate cap: YamBMS defaults to 0.5C, so 428 Ah x 0.5 = 214 A. The lowest is 174 A, so frame 0x351 carries a 174 A charge limit. At 52 V that is about 9.0 kW.
Discharge works the same way. The user ceiling is 37 + 37 + 150 = 224 A, but the C-rate cap is still 214 A, so the bridge sends 214 A, not 224 A. That gap proves the bridge is doing maths. At 52 V, 214 A is about 11.1 kW. The 8 kW Deye pulls at most about 154 A, so the inverter is the real limit here.
| Pack | Ah | kWh | Cells | SOC | Pack volts | Charge limit | Discharge limit |
|---|---|---|---|---|---|---|---|
| A. US3000C | 74 | 3.552 | 15 | 62% | 52.1 V | 37 A | 37 A |
| B. US3000C | 74 | 3.552 | 15 | 58% | 51.9 V | 37 A | 37 A |
| C. DIY 16S, JK | 280 | 14.336 | 16 | 55% | 52.3 V | 100 A | 150 A |
| Virtual battery | 428 | 21.44 | – | 57% | 52.1 V | 174 A | 214 A |
| What the inverter sees | Before the bridge | After the bridge |
|---|---|---|
| Amp-hours | 74 Ah | 428 Ah |
| SOC | 62%, pack A only | 57%, weighted |
| Charge volt limit | 53.5 V | 53.5 V |
| Charge current limit | 37 A | 174 A |
| Discharge current limit | 37 A | 214 A (0.5C cap) |

The lowest cell volt governs discharge: 3.24 V in pack C on our rig. The highest cell governs charge: 3.49 V in pack A. The bridge sends both, with the cell ID. When one cell runs ahead near the top, YamBMS trims the charge volt. When one cell lags near the bottom, it trims the discharge current. That is why BMS volts must be set right: a BMS that reads 0.05 V high will cut charge early on bad data.
Build it in order: ten steps, each with a check
Work the steps in order. If a check fails, stop there. Do not skip ahead.
- Write down each pack alone. Meter each pack at its own posts: volts, SOC, amp-hours, and cell count. Check: three rows in hand, one per pack. If a pack shows no SOC, wake its BMS first.
- Check the packs can be linked. All three packs must share one chemistry and one nominal volts: LiFePO4, 48 V. Pack volts must sit within 0.5 V of each other: our rig read 52.1 V, 51.9 V, and 52.3 V. Check: spread is 0.5 V or less. If it is more, fix the odd pack first.
- Fuse each pack and wire to a busbar. Give each pack its own DC fuse. Our rig uses 100 A fuses on the two Pylontech strings and a 200 A fuse on the JK string. Use equal length cables from each pack to the busbar. Check: one fuse per pack, cables the same length. If one pack has no fuse, stop and fit one.
- Link the Pylontech pair. Chain pack A Link Port 1 to pack B Link Port 0. Pack A keeps Link Port 0 empty, so it is master. Set all four DIP switches to 0 on both packs; DIP2 at 0 keeps the CAN end resistor on. Check: pack A Link Port 0 is empty, DIP switches read 0000.
- Wire the JK pack to the bridge. Connect the JK BMS RS485 link to the ESP32 node. The bridge is the only talker to the inverter. Check: the JK link lands on the bridge, not on the inverter port.
- Set the bridge profile. Pick the Deye brand in YamBMS and leave the protocol on Automatic, which gives PYLON V1 and Lithium Mode 00. Set the C-rate to 0.5C, the user charge ceiling to 174 A, and the discharge ceiling to 224 A. Check: the bridge shows Deye, PYLON V1, Lithium Mode 00. If it shows Not defined, nothing is sent yet.
- Check the bridge dashboard. All three BMS units must show as combined, with totals of 428 Ah, 57% SOC, and a 174 A charge limit. Check: BMS count 3, BMS combined 3. If one pack shows as not combined, check its link and volt calibration.
- Plug the bridge CAN link to the inverter. Use pins 4 and 5 for CAN-H and CAN-L, pin 6 for ground, at 500 kbps, with a 120 ohm end resistor at each end. The same CAN pins show up in the same-day SMA Sunny Island pinout. Check: about 60 ohms between CAN-H and CAN-L with power off.
- Power up in order. Battery first, then the bridge, then the inverter. Wait two full minutes. Check: the inverter shows 57% SOC, 52.1 V, and a 174 A charge limit. If it still shows 62% and 37 A, it is still reading pack A direct. If it shows 0 Ah, see the same-day Sol-Ark capacity 0 fix.
- Prove it under load and on charge. Run a 3 kW load for one hour. That is 3 kWh, or 14% of the bank, so SOC should read about 43%. Then charge at 4 kW for 30 minutes: 2 kWh more, about 9 points. Check: SOC moves both ways and lands near the worked numbers.
Read the meter: what the numbers mean
A meter settles most fights about a dead link. The inverter screen can lag, but the meter at the pack posts is the truth. Read each pack alone first, then the busbar, within 0.1 V of each pack. If not, a cable or a fuse is adding drop.
| When you read it | Reading on our rig | What it means |
|---|---|---|
| Each pack alone. | 52.1 V. 51.9 V. 52.3 V. | Spread 0.4 V. Safe to link. |
| Inverter screen, before bridge. | 62% SOC. 37 A limit. | Inverter sees pack A only. |
| Inverter screen, after bridge. | 57% SOC. 174 A limit. | Bridge sum is live. |
| Frame 0x351 on the bus. | 53.5 V. 174 A. 214 A. | Charge volt and amps. |
| After 3 kW for 1 hour. | SOC about 43%. | Bank gave 3 kWh. |

If the inverter shows 62% after the bridge is on, it is still reading pack A direct, so pull the old CAN cable from pack A. If SOC reads 100% while the packs sit at 57%, one BMS is sending a false full flag. YamBMS only sends 100% when the bank is truly full.
What can still go wrong
One pack drops off the bus and the totals shrink with no alarm.
A BMS can go quiet if its link cable works loose or its RS485 port sleeps. YamBMS then drops that pack from the sum. On our rig, losing pack C would cut the bank from 428 Ah to 148 Ah. Watch the combined count each week. If it reads 2 of 3, find the dead link first.
The 0.5C cap cuts your discharge limit below the sum of the packs.
The packs sum to 224 A of discharge, but the bridge sends 214 A. That is the 0.5C cap: 428 Ah times 0.5 is 214 A. It is the bridge guarding the cells. Raise the C-rate only if your cell maker rates the cells for it.
DVCC sends the full charge limit to each charger, not a share.
This one bites Victron rigs with two chargers. The DVCC guide says the charge current limit is not shared between inverter and chargers: each unit gets the full CCL. Two chargers at 174 A each is 348 A into a 174 A bank. With route 3 and two charge sources, set a system-wide cap in DVCC. This is stated in the Victron DVCC guide, section 12.3.1.
The 15S and 16S mix leaves the big pack part full.
The bridge caps charge volts at 53.5 V, so the 16S pack tops out near 3.34 V per cell and never reaches 100%. Over time its SOC will read low, and its share of the work will shrink. For every pack full, build all packs with the same cell count.
A volt spread at link time trips over-current protection.
Link two packs with a big volt gap and a surge flows from the high pack to the low one. The Eneronix guide works the maths: a 1.5 V gap can push 40 A to 60 A, and a 5 V gap can push past 100 A. The BMS over-current protection may trip, and the bank will not run right until it is reset. Match SOC within about 2% and volts within 0.5 V before you link.
Common questions
Can I just plug three BMS CAN cables into one inverter port?
No. The inverter port takes one battery. Two packs sending the same CAN frame IDs overwrite each other, so the charge limit and SOC flip each second. Use a bridge, or stack packs of one brand.
Will the inverter charge all three packs at the same rate?
No. The bridge sets one total limit for the bank. The current then splits by pack volts, cable length, and SOC: the fuller pack takes less, the emptier pack takes more. Equal length cables keep the split fair. That is why step 3 matters.
Can I mix 15S and 16S packs in one bank?
Yes, with a bridge. The bridge must cap the charge volts at the lower pack’s full volts, 53.5 V here, so the 16S pack never fills past about 3.34 V per cell. You lose the top of the big pack. Do not mix them in a native stack, which needs the same cell count.
What happens if one BMS drops out?
The bridge drops that pack from the sum. The amp-hours, the SOC, and the limits all fall to match the packs that are left, and the inverter keeps running on the smaller bank. That is safe but silent, so check the combined count often. A bank that shrank without you knowing will cut out early under load.
Do I still need a fuse on each pack?
Yes. Fuse each pack on its own. A short in one pack must not pull current from the other two through the busbar. Our rig uses 100 A fuses on the Pylontech strings and a 200 A fuse on the JK string.
Do this next
- Meter each pack alone and write down volts, SOC, and amp-hours.
- Check the spread: same chemistry and volts, within 0.5 V.
- Fuse each pack and wire to one busbar.
- Pick your route: stacking for one brand, YamBMS for mixed brands, Venus OS for Victron.
- Set the bridge profile and check the totals: 428 Ah, 57%, 174 A.
- Plug only the bridge CAN link to the inverter, pins 4 and 5, and test at 60 ohms.
- Power up battery, bridge, then inverter, and check the SOC.
- Prove it: 3 kW for one hour should drop SOC about 14 points, and 4 kW for 30 minutes should lift it 9 points.
- Still stuck? Read the YamBMS build guide or the dbus-serialbattery install for your route, and check the Open-Loop hub for the other bridge guides.
Sources
Checked on 25 November 2026. Unconfirmed items are labelled “not confirmed” in the text.
- YamBMS, Sleeper85, GitHub. ESPHome project, GPL-3.0, since August 2024. Parallel packs only, never series. Sends PYLON, SMA, Victron, or LuxPower talk over CAN or RS485: volts, current, SOC, SOH, charge and discharge limits, min and max cell volts with cell ID, temps, and alarms. SOC 100% is sent only when the bank is fully charged.
- YamBMS behavior notes. A BMS joins the sum only when it is online and its capacity reads above 0. If one BMS blocks charge, the current falls.
- YamBMS functions notes. Charge current is the lowest of three values: a user ceiling, the sum of BMS over-current values times 0.9, and a C-rate value from capacity, default 0.5C. With more than one inverter declared, CCL and DCL are split by the count of links.
- WIZnet Makers, How Does YamBMS Merge Multiple ESS BMS Units. Merges seven BMS families: JK, JBD, Seplos, PACE, BASEN, DEYE, Ecoworthy. 28 inverter models from 13 brands listed as confirmed working. Temp table: 0.05C at 0 degrees, zero below 0 and at 60 degrees.
- dbus-serialbattery, mr-manuel, GitHub. Battery monitor driver for Venus OS GX devices. Talks to a BMS over serial RS232, RS485, TTL UART, or Bluetooth, then puts SOC and limits on the Venus OS bus. First version September 2020, kept by mr-manuel since February 2023. It publishes MaxChargeCurrent, MaxDischargeCurrent, MaxChargeVoltage, and BatteryLowVoltage for DVCC.
- dbus-serialbattery supported BMS list. Most used: JKBMS 68%, JBD 13%, Daly 12%. The docs call for a unique ID per BMS in a multiple battery setup. Which limit DVCC follows when several serial batteries are present at once is not confirmed in the docs read for this guide.
- Pylontech US3000C Operation Manual, Information Version 20CQSV1103, via manua.ls. 48 V nominal, 15 cells, 3,552 Wh, 74 Ah, 95% depth of discharge, charge 52.5 to 53.5 V, recommended 37 A, max 74 to 89 A for 60 seconds. Max 16 packs in one group. Master is the pack with an empty Link Port 0. DIP1 sets RS485 baud, 0 for 115200 and 1 for 9600. DIP2 sets the CAN end resistor, 0 for connected.
- Eneronix, How to Wire Pylontech Batteries in Parallel. Master is set by chain place, not by a DIP switch. Match SOC within about 2% before you link. A 1.5 V gap can push 40 A to 60 A, a 5 V gap can push past 100 A. Fuse each US3000C string at 100 A. Use a busbar for four or more packs.
- Setfire Labs, Pylontech CAN frames. CAN at 500 kbps, frames once per second. Frame 0x351 holds charge volts, charge amps, and discharge amps. Frame 0x355 holds SOC and SOH. Frame 0x356 holds volts, current, and temp. Frame 0x35E holds the maker name “PYLON”. Newer packs use 0x35A and 0x35F in place of 0x359 and 0x35C.
- Victron DVCC guide. With a managed CAN-bus battery, the GX takes CVL, CCL, and DCL from the BMS. If the BMS limit and the user limit differ, the lower one wins. The CCL is not shared between inverter and chargers: each unit gets the full CCL.
- This site: Open-Loop hub, YamBMS build guide, dbus-serialbattery install, ESPHome JK BMS, SMA Sunny Island pinout.