What this guide works from. One rig: a SolaX X1-Hybrid-5.0-D, one Pylontech stack of four H48050 modules with one SC0500A-100S master controller, 192 V nominal, 9.6 kWh, 50 Ah. The cable was 3 m long. The battery type showed Lead-acid until the link came up.
The short answer. On a SolaX X1 or X3 Hybrid, CAN lives on pins 4 and 5 of the BMS port, and RS485 lives on pins 7 and 8. SolaX Triple Power batteries talk CAN, on pins 4 and 5. Pylontech talks RS485, on pins 7 and 8. Wire a Pylontech stack to the CAN pins and the inverter hears nothing, shows BMS Communication Lost, and leaves the battery type on Lead-acid. Move the same two wires to pins 7 and 8 and the link comes up.
The rig that would not talk
The X1-Hybrid-5.0-D sat on the wall. Below it sat a Pylontech rack: four H48050 modules in a row, each 48 V, 50 Ah, and 2.4 kWh, under one SC0500A-100S master controller. BMS means battery management system, the board that guards the pack. Four modules times 48 V is 192 V. Four times 2.4 kWh is 9.6 kWh.
The owner had picked the right shape of pack. The manual gives a battery volt range of 85 to 400 V, and it names 2 to 7 H48050 modules with one SC0500A-100S as the Pylontech set-up.
At rest the rack read 194.4 V at 62% charge. SOC means state of charge, how full the pack is. Four modules hold 60 cells, so 194.4 V divided by 60 is 3.24 V per cell. The top is 54 V per module, so 216 V for the rack. The floor is 45 V per module, so 180 V.
Then the owner wired the comms cable to the CAN pins. He had read online that CAN is the link to use. He crimped the blue pair, pins 4 and 5, to the CAN port on the master controller. The inverter screen showed the pack volts, 194.4 V. But it showed no SOC, no charge limit, and no discharge limit. The battery type still showed Lead-acid. A minute later it showed BMS Communication Lost.
He reseated both plugs and tried a second cable on the same pins. Nothing changed. The fault was the pin pair.
After the fix, the cable moved to RS485 pins 7 and 8 and the RS485 port on the master controller. The battery type flipped to lithium on its own. The SOC showed 62% in under a minute, and the charge limit showed 30 A. A 1,500 W heater ran for ten minutes. It pulled 7.7 A from the pack. That is 1,500 divided by 194.4. It used 250 Wh. SOC fell from 62% to 59%. Then the sun charged the pack at 10 A for 15 minutes. That added 2.5 Ah. SOC rose from 59% to 64%.
What the pins carry
The SolaX BMS port is one RJ45 socket at the bottom of the inverter. The X1-Hybrid manual, page 30, prints the pin table. Read the pins with the clip facing away from you.
| Pin | Wire colour (T-568B) | X1-Hybrid (manual, p. 30) | X3-Hybrid (manual, p. 66) | X1/X3 Hybrid G4 (manual, p. 49) |
|---|---|---|---|---|
| 1 | White/orange | NTC | No link | BAT_TEMP |
| 2 | Orange | GND | GND | GND |
| 3 | White/green | GND | No link | GND |
| 4 | Blue | BMS_CANH | BMS_CANH | BMS_CANH |
| 5 | White/blue | BMS_CANL | BMS_CANL | BMS_CANL |
| 6 | Green | No link | GND | No link |
| 7 | White/brown | BMS_485A | BMS_485A | BMS_485A |
| 8 | Brown | BMS_485B | BMS_485B | BMS_485B |

Read the two middle pairs twice. Pins 4 and 5 are CAN on all three manuals. Pins 7 and 8 are RS485 on all three manuals. Pin 1 is a temp sensor on the X1: NTC on the older manual, BAT_TEMP on the G4 manual. Do not wire pins 1, 3, or 6 for a lithium link.
The G4 manual adds one line that matters: the comms port on the lithium battery must match pins 4, 5, 7, and 8. So the battery side uses the same pin numbers.
The manual also says which pair goes with which battery: “Battery BMS module (Pylontech: RS485 port; Triple Power: CAN port).” So a Pylontech stack goes on pins 7 and 8, and a Triple Power stack goes on pins 4 and 5.
| Link | Battery | Inverter pins | Battery port | Wire pair (T-568B) | Speed |
|---|---|---|---|---|---|
| CAN | SolaX Triple Power | 4 CAN-H, 5 CAN-L | CAN port | Blue, white/blue | 500 kbps |
| RS485 | Pylontech H48050 + SC0500A | 7 485A, 8 485B | RS485 port | White/brown, brown | Not stated in the SolaX manual |
| CAN | Pylontech US3000C (48 V pack) | 4 CAN-H, 5 CAN-L | CAN port | Blue, white/blue | 500 kbps, 120 ohm |

That last row needs a warning. A US3000C is a 48 V pack. It does not fit any X1 or X3 Hybrid: the smallest volt floor on these inverters is 80 V. Its own manual says do not link the modules in series. So the US3000C row shows the pin order only. For the full 48 V Pylontech pin story, see the Pylontech US2000C, US3000C and US5000 pinout guide.
Ground is the orange wire on pin 2, on all three manuals. Keep only the wires you need in the plug. For CAN, keep blue, white/blue, and orange. For RS485, keep white/brown, brown, and orange. Cut the rest back and tape the ends.
CAN-H and CAN-L must sit on one twisted pair: blue and white/blue, pins 4 and 5. RS485 A and B must sit on one twisted pair too: white/brown and brown, pins 7 and 8. Do not split a pair across two wire colours. The same no-talk fault on a Fox ESS comes from a swapped CAN pair instead, and on a Growatt from the wrong program code. See the Fox ESS H1 and AC1 BMS port pinout guide and the Growatt SPF 5000 ES BMS pinout guide.
Which socket is which
The bottom of a SolaX inverter holds more than one RJ45 socket. Only one takes the battery cable.
The BMS port is the battery socket. On the X1-Hybrid it sits at the bottom of the inverter, next to the BAT power terminals. Push the cable connector in and screw it tight. On the X1-Hybrid G4 M series, the battery port line is on the X1-Matebox, and you just plug it in there.
The other sockets sit near it. The COM port is for Modbus and add-on gear, not for the battery. On the G4, the COM port also uses pins 4 and 5 for RS485, which is a trap: same pin numbers, wrong socket. The CAN1 and CAN2 ports on the X3 link two inverters that work as one. The Meter/CT port takes the export meter or the CT clamp.
Our rig had the cable in the right socket. The fault was which pins the cable used. The X3 takes the same BMS port and pin order. The X3-Hybrid G4 takes a higher volt range, 180 to 800 V, and its battery list starts at two T30 modules, not one.
Why a wrong pair breaks the handshake
Think of the handshake as a short call the two boxes make again and again. The inverter asks the BMS for data. The BMS answers with a frame, one short packet that holds SOC, charge and discharge limits, cell volts, and temps. If no answer comes back in time, the inverter stops trusting the pack and raises BMS Communication Lost.
CAN and RS485 are two different tongues. A CAN frame means nothing to an RS485 port, and an RS485 frame means nothing to a CAN port. Our rig had the inverter listening on CAN, pins 4 and 5, while the Pylontech master controller was set to talk RS485. Both boxes were awake. Neither heard the other.
That is also why the battery type stayed on Lead-acid. The manual says the type flips to lithium on its own once the BMS is linked. No link, no flip. If it still says Lead-acid after two minutes, the link is dead. Do not set it by hand: a manual change loses all the charger settings.
CAN works as a pair. At rest, both lines sit near 2.5 V. To send a bit, the sender pulls CAN-H up toward 3.5 V and CAN-L down toward 1.5 V. A plain meter reads the average, near 2.5 V on each line. That is why the meter read 2.5 V on pins 4 and 5 in our rig even though no frames got through.
RS485 works a different way. It sends data as a small volt gap between the A and B wires. When the bus is quiet, the gap sits near 0 V. When frames pass, a plain meter across the two wires jumps. That jump is the test: a live RS485 pair moves, a dead one does not. Most comms faults are fixed with no new parts. The same-day Pylontech to SMA Sunny Island guide shows a different brand where the end resistor, not the pin pair, is the usual fault.
Fix it in order: ten steps, each with a check
Work the steps in order. If a check fails, stop there. High-voltage DC can kill. Wait five minutes after you switch everything off before you touch a terminal.
- Write down what you see. Note the pack volts, the SOC on the BMS, and the fault name exactly as the screen shows it. Check: volts, SOC, and fault name in hand.
- Check the pack volts sit inside the inverter window. The X1-Hybrid takes 85 to 400 V. Our rack read 194.4 V. The G4 takes 80 to 480 V, and the X3-Hybrid G4 takes 180 to 800 V. Check: volts inside your model’s window.
- Check the battery type on the screen. With a lithium pack and a dead link, it shows Lead-acid. Do not change it by hand. Check: type shows Lead-acid now.
- Find the BMS port. It sits at the bottom of the inverter, next to the BAT terminals. Check: the battery cable is in the BMS port.
- Check which pair the cable uses. Pylontech uses RS485, pins 7 and 8. Triple Power uses CAN, pins 4 and 5. Check: the pair matches your battery brand.
- Test the cable with the power off. Meter each wire end to end. Expect less than 1 ohm per wire, and no short between pins. Check: each wire under 1 ohm, no shorts.
- Build or fix the cable. At the inverter end, white/brown goes to pin 7 and brown to pin 8. Orange goes to pin 2 for ground. At the battery end, plug into the RS485 port on the master controller. Check: pins 7 and 8 at both ends.
- Meter the live bus. Power on, bus idle. Each CAN line should sit near 2.5 V to ground. Across the RS485 pair, the meter should jump while frames pass. Check: CAN lines near 2.5 V, RS485 pair jumping.
- Power up in order and wait. Battery first, then PV, then AC. Wait two full minutes. On our rig the type flipped to lithium and the SOC showed 62% in under a minute. Check: type shows lithium, SOC matches the BMS.
- Prove it under load and on charge. Put a 1,500 W load on the house for ten minutes. It pulled 7.7 A. That is 1,500 divided by 194.4. Over ten minutes it used 250 Wh. SOC fell from 62% to 59%. Then let the sun charge the pack at 10 A for 15 minutes. That added 2.5 Ah. SOC rose from 59% to 64%. Check: SOC moves down on load and up on charge.
Read the meter: what the numbers mean
A meter settles most fights about a dead link. All volt numbers are DC to ground.
| When you read it | Reading on our rig | What it means |
|---|---|---|
| Rack at rest, before the fix. | 194.4 V, 62% SOC. | Rack healthy, 3.24 V per cell, BMS awake. |
| CAN lines, power on, idle, before. | 2.5 V each. | Port alive, no frames get through. |
| RS485 pair, power on, before. | Near 0 V, no movement. | Nothing on the RS485 pair. Cable was on CAN. |
| Cable wires, power off. | Under 1 ohm each. | Cable is sound. The fault is the pin pair. |
| Battery type, before. | Lead-acid. | Link is dead. It flips on its own when the link works. |
| RS485 pair, power on, after. | Meter jumps while frames pass. | Link is alive. |
| Inverter SOC, after. | 62%, 194.4 V, 30 A limit. | Link is live. |
| Load: 1,500 W, 10 min. | 7.7 A, SOC 62% to 59%. | Pack feeds the house. |
| Charge: 10 A, 15 min. | 2.5 Ah, SOC 59% to 64%. | Pack takes charge. |

The 2.5 V CAN reading is the one that fools people. It only proves the CAN transceiver has power. It says nothing about frames. The RS485 jump test tells the truth for a Pylontech stack. A dead pair sits still. A live pair moves.
The rack charges up to 216 V and discharges down to 180 V. That is 3.60 V per cell at the top and 3.00 V per cell at the floor. Our rig charged at 10 A, well inside the 30 A max for the 5.0 model. At 30 A and 194.4 V, the most the inverter can pull is 5,832 W.
What each symptom points to
Match what you see to the row below, then work the fix in that row.
| What you see | Most likely cause | Fix |
|---|---|---|
| BMS Communication Lost, no SOC, pack volts show. | Cable on the CAN pair with a Pylontech stack. | Step 7, move the cable to pins 7 and 8. |
| BMS Communication Lost, no SOC, Triple Power pack. | Cable on the RS485 pair with a Triple Power stack. | Step 7, move the cable to pins 4 and 5. |
| BMS Lost, IE 19, on a G4. | Link is down. | Steps 4 to 7, check the socket and the pair. |
| Bat Volt Fault, no battery data. | Pack volts outside the window. | Step 2, check the volts. A 48 V pack will not work. |
| BatConDir Fault. | Battery plus and minus are swapped. | Stop. Fix the power wires. Do not restart it. |
| No fault, but screen shows volts only. | Cable in the wrong socket. | Step 4, move it to the BMS port. |
| No SOC, a wire reads open circuit. | Cable cut, or a plug is out. | Steps 6 and 7. |
| SOC shows, then drops out under load. | Ground wire missing, pin 2 open. | Step 7, check the orange wire. |
| Link works, then dies at noon. | Cable tight against DC or AC power cables. | Move the cable away from power cables. |

The first row is the one most owners hit. A new build, a good pack, and BMS Communication Lost in the first minute. It is almost always the wrong pair. See the same-day Axpert Error 69 and Error 70 guide and the same-day LiFePO4 float voltage guide.
What can still go wrong
A US3000C pack does not fit any X1 or X3 Hybrid, at any pinout.
This is the most common mix-up with SolaX. The US3000C is a 48 V pack. Every X1 and X3 Hybrid needs a high-volt pack: 85 to 400 V on the older X1, 80 to 480 V on the X1 G4, 180 to 800 V on the X3 G4. Its own manual says do not link the modules in series. The right Pylontech pack is the H48050 stack with an SC0500A master controller, 2 to 7 modules in series. Some third-party pages call the older X1 and X3 a 48 V inverter. That is wrong: the module is 48 V, but the stack is high volt.
The G4 takes SolaX batteries only, on the official list.
The SolaX battery guide for the G4 lists Triple Power only: T30, T58, HS25 and HS36, HS51 and HS51O. It lists no Pylontech pack for the G4.
The COM port also uses pins 4 and 5 for RS485, and that is a trap.
On the G4, the COM port carries Modbus RS485 on pins 4 and 5, with ground on pin 6. Those are the same pin numbers as CAN on the BMS port, but it is a different socket for a different job. A cable in the COM port will never bring the battery up. The X3 has CAN1 and CAN2 ports too, for parallel inverters. The battery still goes to the BMS port.
The end resistor and cable length are not confirmed in the SolaX manuals.
The CAN standard calls for a 120-ohm resistor at each end of the bus, which reads about 60 ohms with the power off. The US3000C manual names 120 ohms for its CAN port. Neither SolaX manual names its own end resistor value, and the SC0500A value is not confirmed in the sources I read. Do not add an end resistor on a guess.
The manual sends Pylontech to RS485, but some installer guides use CAN for Pylontech too.
The SolaX manual’s own words send Pylontech to the RS485 port and Triple Power to the CAN port. Some installer guides show a CAN choice for Pylontech as well. The manual path is the one this guide follows. Whether a CAN link to a Pylontech stack works on a given firmware is not confirmed in the SolaX manual.
Common questions
Which pins carry CAN on a SolaX X1 or X3 Hybrid?
Pins 4 and 5. Pin 4 is CAN-H and pin 5 is CAN-L, on the X1, the X3, and the G4. Pin 2 is ground. That is from the SolaX manuals: X1 page 30, X3 page 66, G4 page 49.
Which pins carry RS485?
Pins 7 and 8. Pin 7 is 485A and pin 8 is 485B, on the X1, the X3, and the G4. A Pylontech stack uses these pins.
Do I need a straight cable or a crossover cable?
A straight pin-to-pin cable, as long as you pick the right pair. The fault in this guide was not a crossover problem. It was the wrong pair: CAN pins with a Pylontech stack.
What does BMS Communication Lost mean?
It means the inverter has stopped getting data from the BMS. The most common causes are the wrong pin pair, the wrong battery port, or the cable in the wrong socket. On a G4 the same fault shows as IE 19 BMS Lost.
Why does the battery type still show Lead-acid?
Because the link is dead. The manual says the type flips to lithium on its own once the BMS is linked. If it still says Lead-acid after two minutes, the link is down.
Will a Pylontech US3000C work on my X1-Hybrid G4?
No. The G4 needs 80 to 480 V. A US3000C is a 48 V pack, and its manual says not to link modules in series. The G4 official battery list is Triple Power only. The Pylontech stack that fits a SolaX Hybrid is the H48050 with an SC0500A master controller, on the older X1 and X3. See the Solis hybrid inverter BMS RJ45 pinout guide for a brand where a 48 V pack does fit.
Do this next
- Read the pin table. Pins 4 and 5 are CAN, pins 7 and 8 are RS485, pin 2 is ground.
- Check your pack volts sit inside your model’s window: 85 to 400 V on the older X1, 80 to 480 V on the X1 G4, 180 to 800 V on the X3 G4.
- Pick the pair for your battery: RS485, pins 7 and 8, for Pylontech; CAN, pins 4 and 5, for Triple Power.
- Wire it pin to pin: white/brown to pin 7, brown to pin 8, orange to pin 2 for ground.
- Plug into the BMS port, not the COM port, and into the RS485 port on the master controller.
- Power the battery first, then PV, then AC, and wait two minutes for the type to flip to lithium.
- Check the screen shows live SOC and a 30 A charge limit, then prove it with a 1,500 W load for ten minutes.
- Still stuck? Call SolaX support with your meter readings and pin map.
Sources
Checked on 27 November 2026. Unconfirmed items are labelled “not confirmed” in the text.
- SolaX X1-Hybrid User Manual, 3.0 kW to 5.0 kW (SolaX official PDF). Page 30: BMS pin table, pin 1 NTC, pin 2 GND, pin 3 GND, pin 4 BMS_CANH, pin 5 BMS_CANL, pin 6 no link, pin 7 BMS_485A, pin 8 BMS_485B. Section 6.4: high-volt lithium battery, max pack volt 400 V, rated pack volt 350 V, lead-acid 85 to 400 V, Pylontech 2 to 7 H48050 modules with 1 SC0500A-100S, SolaX 1 to 3 HV10045/HV10063 with 1 MC0500, Pylontech RS485 port and Triple Power CAN port. Section 4.3: battery 85 to 400 V, preferred 300 VDC, capacity 4.8 to 16.8 kWh, max charge and discharge 30 A, CAN/RS485. Page 33: battery type flips to lithium on its own once the BMS is linked. Pages 72 to 73: BMS Communication Lost, BMS Lost, BMS_External_Err, Bat Volt Fault, BatConDir Fault.
- SolaX X1-Hybrid G4 Series User Manual. Page 26: BMS port definition, pin 1 BAT_TEMP, pin 2 GND, pin 3 GND, pin 4 BMS_CANH, pin 5 BMS_CANL, pin 6 no link, pin 7 BMS_485A, pin 8 BMS_485B. Page 29: battery comms port must match pins 4, 5, 7, and 8. Page 12: battery full volt range 80 to 480 V, max charge and discharge 30 A. M series battery port line is on the X1-Matebox.
- SolaX X3-Hybrid Series User Manual, 5.0 kW to 15.0 kW. Page 66: BMS pin table, pin 4 BMS_CANH, pin 5 BMS_CANL, pin 7 BMS_485A, pin 8 BMS_485B, and the note that the battery comms port must match pins 4, 5, 7, and 8. CAN1 and CAN2 ports link parallel inverters.
- SolaX X1/X3 Hybrid G4 Battery Selection V1.2, 6 August 2026. X1 Hybrid G4 battery port 80 to 480 V, max 30 A. X3 Hybrid G4 battery port 180 to 800 V, max 30 A. Battery lists are Triple Power only: T30, T58, HS25/36, HS51/51O. No Pylontech pack is listed for the G4.
- Pylontech H48050 High-Voltage Lithium Battery Module. 48 V nominal, 45 to 54 V range, 50 Ah, 2.4 kWh, 15 cells, CAN and RS485, up to 7 modules in series.
- Pylontech SC0500-100S BMS Master Controller. 100 to 430 V, 100 A max charge and discharge, CAN and RS485 ports, made to control H48050 modules.
- Pylontech US3000C Operation Manual, Information Version V1.0. 48 V nominal, discharge 44.5 to 53.5 V, charge 52.5 to 53.5 V, 3,552 Wh. CAN 500 kbps, 120 ohm. RS485 9600 or 115200 bps, 120 ohm. RJ45 pins 1 to 3 null, pin 4 CAN-H, pin 5 CAN-L, pin 6 CAN-GND, pin 7 485A, pin 8 485B. Do not link modules in series.
- SolaX Battery Communication Fault: Causes and Fixes, SolaX Australia. A comms fault means the inverter and battery have lost their data talk, not that either box has failed. Wrong pinout on a site-made cable is named as a cause. Wait at least five minutes after power off before work.
- SolaX BatPowerLow and Battery Not Charging Guide, SolarNevs, 18 September 2026. IE 19 BMS Lost signals battery communication lost. Charger menu max charge and discharge default 30 A. Five-minute capacitor wait.
- SolaX Inverter Error Codes Guide, Deionno Electrical. BMS Lost, Bat Volt Fault, and EPS Overload Fault come from the X1-Hybrid range.
- SolaX X1/X3-Hybrid G4 Corrected Modbus RTU Map, TapHome. G4 COM port pins 4 485A, 5 485B, 6 GND, pin 3 +13V, CAT5E cable, max 30 m. COM port is for Modbus, not for the battery.
- ISO 11898-2 CAN standard (PCBCool). Idle near 2.5 V per line, dominant CAN-H toward 3.5 V and CAN-L toward 1.5 V, 120-ohm resistor at each end, about 60 ohms measured with power off.
- This site: RJ45 Pinouts hub, Pylontech US2000C, US3000C and US5000 pinout guide, Fox ESS H1 and AC1 BMS port pinout, Growatt SPF 5000 ES BMS pinout, Solis hybrid inverter BMS RJ45 pinout, Pylontech to SMA Sunny Island CAN guide, Axpert Error 69 and Error 70 guide, LiFePO4 float voltage guide.