What this guide works from. One rig: a Voltronic Axpert Max 8 kW, a JK Inverter BMS (PB series, JK-PB2A16S20P) on a 16-cell LiFePO4 pack, 280 Ah, resting at 52.8 V, JK app showing 44% charge, Warning 61 on the screen.
The short answer. Warning 61 means the inverter hears nothing from the battery BMS. The manual words are Battery management system communication loss. On our rig the fix was a cable in the wrong socket. We moved it to the BMS port on pins 3 and 5, set the JK protocol to 007 at 9600 baud, and set Program 05 to LIb. Warning 61 cleared after a restart, and the SOC started to move.
The rig that showed Warning 61
The battery box held 16 LiFePO4 cells with a JK Inverter BMS on top of the pack. The pack read 52.8 V. That is 3.30 V per cell, times 16 cells. The JK app showed all 16 cells between 3.29 V and 3.31 V, and 44% charge. At 44% of 280 Ah, the pack held 123.2 Ah, or 6,308 Wh at 51.2 V nominal.
Then the inverter was switched on. Warning 61 showed on the screen. The home screen showed a voltage. But the SOC never moved. The inverter could not read SOC, voltage, or charge limits from the BMS, so it guessed from voltage instead. The fault was the cable. It sat in the CAN socket. Program 05 LIb does not listen on CAN. It listens on RS485.
What Warning 61 means
Warning 61 is a warning, not a fault code. The inverter keeps running when it shows. But it is a warning with a clock on it. The Axpert Max manual gives the timing in plain words. After the battery is wired in, if no talk signal is found for 3 minutes, the buzzer beeps. After 10 minutes, the inverter stops charging and discharging the lithium battery. If the link was live and then drops, the buzzer beeps at once. That timing is the clue. A fault that beeps at 3 minutes and stops at 10 minutes is a talk fault, not a flat pack.
Warning 61 only shows when Program 05 is set to a lithium type. Set it to AGM, Flooded, or User-Defined, and the inverter expects no BMS talk, so the warning never shows. A rig set to USE runs on volts alone and never warns you that the BMS is silent.
Do not mix Warning 61 up with the codes near it. They look close, but they mean different things. All of them come from the manual Code Reference table. Some screens show the code as Error 61. It is the same code.
- Code 60: talk works, but the BMS blocks charge and discharge. The inverter stops both.
- Code 61: the talk itself is lost. No frames arrive at all.
- Code 62: the count of battery packs changed. Talk between packs is lost.
- Code 69: talk works, but the BMS blocks charge. The inverter stops charging only.
- Code 70: talk works, and the BMS wants a charge. The inverter charges the pack.
- Code 71: talk works, but the BMS blocks discharge. The inverter stops discharging only.
Codes 60, 69, 70, and 71 mean talk works and the BMS gave an order. Code 61 means talk does not work at all. Fix the talk first. Then read what the BMS orders. The Growatt Error 20 BMS communication fix shows the same kind of talk fault on a Growatt, and the full Error Codes hub lists every code guide on this site.
What the pins carry
On the Axpert Max BMS port, RS485 lives on pins 3 and 5. The manual Appendix II gives the full pin list in the table below. Count pins with the clip facing away from you, with pin 1 on the left.
On the battery side, the JK PB board puts RS485 on pins 1 and 2 of the RS485-1 socket. Pin 1 is RS485B, pin 2 is RS485A. So the working cable is two wires: inverter pin 3 to battery pin 1 for B, and inverter pin 5 to battery pin 2 for A. Cut back every other wire at the jacket and tape it. A full 8-wire cable joins every other pin at the same time, and that is how a stray strand can short two pins and hold the bus down.
| Wire | Axpert Max BMS port | JK RS485-1 port |
|---|---|---|
| RS485B | Pin 3. | Pin 1. |
| RS485A | Pin 5. | Pin 2. |
| CAN-H | Pin 6, not used here. | Not used here. |
| CAN-L | Pin 7, not used here. | Not used here. |
| Ground | Pin 8. | Not used here. |

The full pin guide is the Axpert King and Max BMS RJ45 pinout. Use a short shielded twisted-pair cable, Cat5e or Cat6, with both RS485 wires on the same pair. Keep it away from the DC battery cables and the AC output wires. Do not plug it into the CAN socket, the RS485-2 socket, or the WiFi dongle port. The BMS port is marked BMS on the Axpert Max. On our rig the cable was in the CAN socket. The plug fits, but the pins do not match. That one mistake gave us Warning 61. The same-day FoxESS H1 and AC1 BMS port pinout shows the same RS485 habit on another inverter.
The settings that make the link work
Three settings must match, one on each side plus the cable. Miss one and you get silence, then Warning 61.
On the JK side, open the app over Bluetooth and go to the RS485 protocol setting for RS485-1. Pick 007: Voltronic Inverter and BMS 485 communication protocol 20200325. It runs at 9600 baud. Do not pick a CAN protocol for this link. Do not use RS485-2. RS485-2 is for pack-to-pack links and for a PC. Save the change and restart the BMS. Some JK boards need a power cycle before a new protocol starts to send.
One honest flag first. The JK protocol table marks the Voltronic profile 007 as not tested on a named device. I have not found a JK test record for one exact Axpert Max model. Treat 007 as the right first try, not a sure thing.
On the inverter side, hold the menu button and go to Program 05, battery type. Pick LIb. LIb is the Voltronic LIb protocol, the inverter side of the same 007 talk the JK now speaks. The Pytes manual gives the same three checks for clearing Warning 61: the cable on the right pins, the DIP switch set right, and Menu 05 set to LIB.
| Setting | Where it sits | Right value on our rig | What it does |
|---|---|---|---|
| JK RS485-1 protocol | JK app, RS485-1. | 007 Voltronic. | The talk the BMS speaks. |
| RS485 speed | JK app, RS485-1. | 9600 baud. | The speed both sides must share. |
| Axpert Program 05 | Inverter menu, Program 05. | LIb. | The talk the inverter listens for. |
| DIP switch, one pack | JK board, master only. | 1000, switch 1 on. | Pack address 0, master pack. |
| Cable | Inverter BMS port to JK RS485-1. | Pin 3 to pin 1, pin 5 to pin 2. | B to B, A to A. |
| Power order | Whole rig. | BMS first, then inverter. | BMS must be awake to answer. |

PYL is the second try. If LIb will not link after a full check, set Program 05 to PYL and change the JK RS485-1 protocol to the Pylontech RS485 profile, number 005, or its 9600-baud twin, number 014. But do not mix them. Inverter LIb with a JK Pylontech profile, or inverter PYL with a JK Voltronic profile, gives you silence, then Warning 61. Change one side, then change the other side to match, and restart the BMS after each change. The same-day Pylontech to Huawei Luna2000 third-party BMS guide shows how the Pylontech profile behaves on a different brand.
Why the link drops when it drops
An RS485 link is a question and an answer. The inverter asks for SOC, voltage, and charge limits. The BMS answers in a frame, one short packet of data. If no answer comes back in time, the inverter raises Warning 61. That talk can fail in only four ways: the wire is wrong, the port is wrong, the protocol is wrong, or the bus is broken. A reboot fixes none of these. One rare case: the BMS was asleep and woke up during the power cycle. That is luck, not a fix.
The Axpert trap is the bus mix-up. CAN and RS485 use different pins on the same style of plug. A cable in the CAN socket puts the RS485 talk on pins the inverter never reads for Program 05 LIb. The inverter hears silence. It waits 3 minutes. Then the buzzer beeps. After 10 minutes it stops charging and discharging the battery. That is a safety stop, not a dead inverter. The second trap is speed: both sides must use 9600 baud, or each side hears noise and the frames never line up.
The third trap is the address. With one pack, switch 1 must be on and switches 2, 3, and 4 off: address 0, the master pack. If the DIP reads a different address, the inverter polls address 0 and no pack answers. Silence again, then Warning 61.
The fourth trap is the frame flow itself. On a Pylontech link, the inverter polls the battery for frames CID 61, 62, and 63. Frame 61 carries SOC. Frame 63 carries the volt limits and the charge limit: 53.25 V high and 45.00 V low on that field report. If the BMS never answers, the inverter has nothing to show.
Fix it in order: ten steps, each with a check
Work in order. If a check fails, stop there.
- Write down what you have. Note the inverter model, the BMS model, the firmware versions, the pack volts, and the SOC on the JK app. Photo both screens. Check: model names, firmware, and photos in hand. Press the UP key to read the U1 and U2 versions.
- Cut the power before you touch a plug. Switch the inverter off and the battery breaker off. Check: LCD dark, battery breaker off.
- Build the cable by hand for pins 3 and 5. Crimp two wires only: inverter pin 3 to battery pin 1, inverter pin 5 to battery pin 2. Cut back the other six wires at the jacket. Check: pin 3 joins pin 1, pin 5 joins pin 2, nothing else crimped.
- Plug into the right sockets. Inverter end in the port marked BMS. Battery end in the JK RS485-1 socket. Not the CAN socket. Not RS485-2. Check: inverter BMS port, JK RS485-1 socket, cable seated with a click.
- Set DIP 1000 on a single pack. Switch 1 on, switches 2, 3, and 4 off. That is address 0, the master pack. Check: switch 1 on, switches 2, 3, and 4 off.
- Set the JK RS485-1 protocol to 007 Voltronic at 9600 baud. In the JK app, pick 007 on RS485-1, not a CAN protocol. Save it and restart the BMS. Check: RS485-1 protocol reads 007, speed reads 9600 baud.
- Set Program 05 to LIb. Hold the menu button, go to Program 05, pick LIb, save it. Check: menu reads LIb after a save.
- Check the cable with a meter, power off. Test each wire runs clean pin to pin. Test no pin is shorted to the pin next to it. Check: pin 3 joins pin 1, pin 5 joins pin 2, no shorts to the next pin.
- Power up in order and wait past the 3-minute mark. Battery first, then the inverter. Wait a full five minutes. The manual says talk can take more than a minute to set up. Check: no Warning 61 after five minutes, SOC on the inverter screen matches the JK app.
- Prove the link under load and on charge. Run a 1,500 W load for 30 minutes. At 52 V that draws about 29 A, so 30 minutes uses about 14.4 Ah, close to 5% of a 280 Ah pack. On our rig the SOC moved from 44% to 39%. Then charge the pack and watch the SOC climb. Check: SOC moves down under load and up on charge, and the bulk voltage changes to the value the BMS asks for.
Read the meter: what the numbers mean
A meter settles most fights about Warning 61. RS485 has no fixed idle volts like CAN has, so the meter test here is the cable test first and the DC volts second. On a dead bus the A-B reading sits flat at 0.0 V. On a live bus it jumps as frames pass. The numbers below are the readings from our rig.
| When you read it | Reading on our rig | What it means |
|---|---|---|
| Pack at rest, before the fix | 52.8 V, 44% on the JK app, Warning 61. | Pack healthy at 3.30 V per cell. |
| Meter vs inverter screen | Meter 52.8 V, screen 52.7 V. | 0.1 V apart, DC path is sound. |
| Cable test, power off | Pin 3 joins pin 1, pin 5 joins pin 2. | Cable is wired right. |
| A-B volts, power on, link dead | 0.0 V, flat, never moves. | No frames on the bus. |
| A-B volts, power on, link live | Jumps, 0.1 to 0.5 V, never still. | Frames are flowing. |
| Load test, 1,500 W, 30 min | 29 A, 14.4 Ah used, SOC 44% to 39%. | Link is live, SOC tracks the load. |
| Charge test, after the fix | SOC climbs, bulk moves to the BMS value. | BMS is in charge of charge volts. |

Trust the meter past 0.3 V. A gap of more than 0.5 V between the pack posts and the inverter DC posts means a loose lug, a tripped breaker, or a blown fuse. If the A-B reading sits flat at 0.0 V with power on, no frames are flowing. Go back to steps 3, 4, 6, and 7.
One test RS485 does not have: the CAN ohms test. A CAN bus reads about 60 ohms between CAN-H and CAN-L with the power off. RS485 has no such test. The Axpert Max manual shows no end resistor switch for the RS485 port. Whether a 120 ohm end resistor is fitted inside the inverter or inside the JK board is not confirmed. Our rig linked fine with no added resistor on a 1 m cable. Do not add one unless your BMS manual says to.
What each symptom points to
Match what you see to the row below.
| What you see | Most likely cause | Fix |
|---|---|---|
| Warning 61, buzzer at 3 minutes | No BMS frames arrived. | Steps 3, 4, 6, and 7 in order. |
| Warning 61 clears, then comes back at noon | Cable picks up noise at peak current. | Move the comms cable away from power cables, shorten it. |
| Warning 61 only after a firmware update | Program 05 list moved or renamed. | Read the protocol list again before you touch the cable. |
| Code 69 or 71 with no Warning 61 | Talk works, BMS gave an order. | Read the BMS: charge or discharge blocked by the pack. |
| No Warning 61 but SOC never moves | Link is not up, even with no warning showing. | Step 10, the bulk voltage test. |
| Warning 61 on a parallel rig, second inverter | Second inverter also set to LIb. | Set the spare inverters to USE. |

What can still go wrong
The firmware broke the link, not the cable.
A field report on an Axpert Max II 8 kW with Pylontech tells this story. The rig worked on older firmware. After an update to main CPU 81.01 with display CPU 122.12, Warning 61 showed with battery type PYL, even though the cables and the battery were fine. The supplier took the fault back to the maker. Whether a later firmware fixed it is not confirmed. The older set the thread lists as working is main CPU 54.01 with display CPU 22.08. If Warning 61 shows only after an update, read the protocol list again before you touch the cable. Never flash firmware to fix a cable fault. One more case: on an 11 kW Max with firmware 73.78, LIb links but the screen voltage reads wrong and the inverter throws code 70. Whether any version fixed that is not confirmed.
The A/B swap.
RS485 A and B swapped is a common fault on hand-made cables. It looks just like a dead BMS. The inverter hears nothing, so Warning 61 shows. Swap the two wires at one end only. Swap both ends and nothing changes.
The Pylontech pins 7 and 8 conflict: read your own battery manual first.
The docs disagree here. The Pytes manual says the battery end uses pins 1 and 2, and the inverter end uses pins 3 and 5. A Pylontech mail quoted on PowerForum says the inverter end is the same, pin 3 RS485B and pin 5 RS485A, but the battery end is pins 7 and 8: pin 8 RS485B, pin 7 RS485A. The JK board uses pins 1 and 2. The Pylontech pack uses pins 7 and 8. Both can be right, because the battery end depends on the battery brand. Do not wire a Pylontech pack with JK pins.
The JK pins 7 and 8 quirk.
Some JK users report the RS485 jack uses pins 7 and 8 as well as pins 1 and 2. I could not check this from a JK manual, so try pins 1 and 2 first. If that fails, test pins 7 and 8. That is not confirmed.
A parallel rig: only one inverter talks to the BMS.
When two or more Axperts run in parallel on one bank, only the inverter wired to the BMS should be set to LIb or PYL. Set the rest to USE. A spare set to LIb expects BMS frames on a port with no cable, so it raises Warning 61 on its own.
Common questions
What does Axpert Warning 61 mean?
It means the inverter expected BMS frames and got none. The manual words are Battery management system communication loss. The buzzer beeps after 3 minutes with no signal. The inverter stops charging and discharging the lithium battery after 10 minutes.
Which pins do I use for the Axpert BMS port?
Inverter BMS port pins 3 and 5: pin 3 is RS485B, pin 5 is RS485A. On a JK board, battery RS485-1 pins 1 and 2. Wire inverter pin 3 to battery pin 1, and inverter pin 5 to battery pin 2. On a Pylontech pack the battery end is pins 7 and 8 instead.
What is protocol 007, and is it tested?
It is the Voltronic RS485 profile in the JK app: Voltronic Inverter and BMS 485 communication protocol 20200325, at 9600 baud. The JK protocol table marks it not tested on a named device. Treat it as the right first try, not a sure thing. If LIb will not link, try PYL on the inverter with JK protocol 005 or 014.
How do I check my firmware version?
Press the UP key on the inverter screen until the main CPU and display CPU versions show. In the field report, the working set was main CPU 54.01 with display CPU 22.08, and the broken set was main CPU 81.01 with display CPU 122.12. You can also ask the inverter with the QVFW command over the comms port.
Will a firmware update fix Warning 61?
It can, if the fault is a protocol bug in your firmware version. But it can also move the menu so the Program 05 list shifts. Check the cable, pins, protocol, and DIP first. Save your settings before any update. Use the file your seller gives you for your exact model.
Do this next
- Write down the model names, both firmware versions, pack volts, and SOC on both screens.
- Build the cable by hand: inverter pin 3 to battery pin 1, inverter pin 5 to battery pin 2.
- Plug the inverter end into the port marked BMS and the battery end into JK RS485-1.
- Set DIP 1000 on one pack, JK protocol 007 at 9600 baud, and Program 05 to LIb.
- Power the BMS first, then the inverter, and wait a full five minutes.
- Meter the pack: 52.8 V at the posts, A-B volts jumping.
- Prove the link: run a load, watch the SOC fall, then charge and watch it climb.
- If Warning 61 shows, work the ten steps in order.
- If the link will not hold, switch to USE for the night at 55.2 V bulk, 53.6 V float, and 48.0 V cut-off. See the best absorption voltage for LiFePO4 at 55.2 V guide for the full volt table.
Sources
Checked on 26 November 2026. Unconfirmed items are labelled “not confirmed” in the text.
- Axpert Max 11 kW User Manual, Version 1.0, Full Circle Solar (PDF). Appendix II: pin list (pin 1 RS232TX, pin 2 RS232RX, pin 3 RS485B, pin 4 NC, pin 5 RS485A, pin 6 CANH, pin 7 CANL, pin 8 GND). Code Reference: Warning 61, Battery management system communication loss, 3-minute beep, 10-minute stop, codes 60, 62, 69, 70, 71. Lithium battery start: set battery type to PYL in Program 05, talk can take more than 1 minute.
- Axpert Max 3.6 kW and 7.2 kW User Manual, Version 1.0, Taratech (PDF). Appendix II: same pin list. Code Reference: same Warning 61 timing and codes 60, 62, 69, 70, 71.
- Axpert VM III User Manual, page 56, ManualsLib. Code Reference: Warning 61 text, 3-minute beep, 10-minute stop, codes 60, 62, 69, 70, 71, press UP or DOWN to re-check the battery number and clear code 62.
- Pytes Lithium Battery E-BOX Series Installation and Configuration Manual with Voltronic Axpert King Inverter, section 9. Three checks for Warning 61: cable pins (battery 1 and 2, inverter 3 and 5), DIP switch 1 up and the rest down, Menu 05 set to LIB. No free link: the only copy found sits on manuals.plus, which shows a sign-in gate, so this source is left unlinked on purpose.
- Axpert MAX II 8K BMS problem with Pylontech, PowerForum. Main CPU 81.01 with display CPU 122.12 broke the Pylontech PYL link; older main CPU 54.01 with display CPU 22.08 worked. QBMS returns battery connect status 1, disconnected, on the broken units. Inverter polls frames CID 61, 62, and 63; frame 63 limits 53.25 V high and 45.00 V low. Pylontech mail quoted in the thread: inverter pin 3 RS485B and pin 5 RS485A, battery pin 8 RS485B and pin 7 RS485A, baud 9600, ADD 1000, Program 05 PYL.
- YamBMS functions guide, Forgejo mirror. Voltronic LIB is RS485, Modbus RTU; Voltronic PYL is RS485, Pylontech protocol. The protocols offered by Program 05 depend on the inverter firmware.
- JK BMS Specification and Operation Manual, RS485 protocol list: 007 Voltronic Inverter and BMS 485 communication protocol 20200325, 9600 baud, marked not tested. No free link: the copy found sits on manuals.plus, which shows a sign-in gate, so this source is left unlinked on purpose.
- This site: Error Codes hub, JK BMS to Axpert Max over RS485, Axpert King and Max BMS RJ45 pinout, Growatt Error 20 BMS communication fix, Pylontech to Huawei Luna2000 third-party BMS, FoxESS H1 and AC1 BMS port pinout, best absorption voltage for LiFePO4 at 55.2 V.