CAN Bus, RS485 & RJ45 Pinouts ✓ BENCH VERIFIED UPDATED NOVEMBER 21, 2026 15 MIN READ 3,134 WORDS

Voltronic Axpert King & Max BMS Port: Which Pin Does What?

Farhan Ahamed
Farhan Ahamed Published November 21, 2026 · 15 min read
0 COMMENTS
Voltronic Axpert King & Max BMS Port: Which Pin Does What?
IN THIS GUIDE · QUICK JUMP KEY SECTIONS
01 · KEY SECTION Jump ↓

The rig that would not link

It was a new build, and it looked right. The Axpert Max 8 kW…

02 · KEY SECTION Jump ↓

What the pins carry

The Axpert Max manual, Appendix II, prints the full pin map for the BMS…

03 · KEY SECTION Jump ↓

Which setting fits your battery

Pins are only half the link. The other half is the setting. The JK…

04 · KEY SECTION Jump ↓

Why the link fails when it fails

An RS485 link is a question and an answer. The inverter asks. The BMS…

05 · KEY SECTION Jump ↓

Fix it in order: nine steps, each with a check

Work the steps in order. If a check fails, stop there.

06 · KEY SECTION Jump ↓

If the reading differs, the reading is the answer

RS485 has no 60 ohm CAN test. The meter test here is the cable…

07 · KEY SECTION Jump ↓

What each symptom points to

Match what you see to the row below. Do not change three things at…

08 · KEY SECTION Jump ↓

King vs Max: same port, different box

King and Max share the BMS port pin map, but the boxes are not…

09 · KEY SECTION Jump ↓

What can still go wrong

Step-by-step field verification & diagnostic reference inside this section.

10 · KEY SECTION Jump ↓

Common questions

Step-by-step field verification & diagnostic reference inside this section.

11 · KEY SECTION Jump ↓

Do this next

Step-by-step field verification & diagnostic reference inside this section.

12 · KEY SECTION Jump ↓

Sources

Checked on 21 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

What this guide works from. One rig: a Voltronic Axpert Max 8 kW, a JK Inverter BMS (PB series, JK-PB2A16S20P) on a 16-cell LiFePO4 pack, 280 Ah, resting at 53.1 V, JK app showing 51% charge, Warning 61 on the screen.

The short answer. The BMS port on an Axpert King and an Axpert Max is one RJ45 socket with three jobs in it. Pins 3 and 5 carry the RS485 link. Pin 3 is RS485B and pin 5 is RS485A. Pins 6 and 7 carry CAN. Pin 6 is CAN-H and pin 7 is CAN-L. Pin 8 is ground. Pin 4 is not used. Pins 1 and 2 are RS232, a PC link, not a battery link. On our rig the cable was wired pin for pin, so the battery RS485 wires landed on pins 1 and 2. The inverter heard nothing. We built a two-wire cable to pins 3 and 5. Warning 61 cleared after a restart, and the SOC started to move.

The rig that would not link

It was a new build, and it looked right. The Axpert Max 8 kW sat on the wall. The battery box held 16 LiFePO4 cells. A JK Inverter BMS sat on top of the pack. The pack read 53.1 V. That is 3.32 V per cell, times 16 cells. The JK app showed all 16 cells between 3.31 V and 3.33 V, and 51% charge. Then the inverter was switched on. Warning 61 showed on the screen. Warning 61 is the battery comms fault. The manual words are Battery management system communication loss. The home screen showed a voltage, but the SOC never moved. SOC is state of charge, how full the pack is. The fault was the cable. It was a shop-bought patch lead, wired straight through, pin 1 to pin 1 and pin 2 to pin 2. That put the battery RS485 wires on inverter pins 1 and 2. Those pins are RS232. RS232 is a PC link. It is not a battery link. The inverter never heard the BMS at all.

What the pins carry

The Axpert Max manual, Appendix II, prints the full pin map for the BMS port. The Axpert King manual, Appendix B, covers the same BMS port. Both manuals print the same eight pins. Count pins with the clip facing away from you, with pin 1 on the left. Pin 1 is RS232TX. Pin 2 is RS232RX. Pin 3 is RS485B. Pin 4 is NC, not connected. Pin 5 is RS485A. Pin 6 is CAN-H. Pin 7 is CAN-L. Pin 8 is ground, marked TERRA in the manual. RS485A and RS485B are the two RS485 wires. CAN-H and CAN-L are the two CAN wires. TX means transmit and RX means receive. NC means the pin joins nothing. Ground is the shared zero-volt line. One socket holds three links at once: RS232, RS485, and CAN. A full eight-wire cable joins all three at the same time. That is the trap. The right cable uses two wires only, and the other six are cut back at the jacket.

PinAxpert King / Max BMS portWhat it does
1RS232TXPC link, transmit. Do not wire a battery here.
2RS232RXPC link, receive. Do not wire a battery here.
3RS485BRS485 link, B wire. Battery pin 1 on a JK BMS.
4NCNot connected. Joins nothing inside the inverter.
5RS485ARS485 link, A wire. Battery pin 2 on a JK BMS.
6CAN-HCAN link, high wire. Not used by Program 05 LIb.
7CAN-LCAN link, low wire. Not used by Program 05 LIb.
8GNDGround. Short runs need no ground wire.
Axpert King and Max BMS port pin map, all 8 pins: 1 RS232TX, 2 RS232RX, 3 RS485B, 4 NC, 5 RS485A, 6 CAN-H, 7 CAN-L, 8 ground
Two-wire RS485 cable for Axpert Max and JK Inverter BMS: JK RS485-1 pin 1 RS485B to Axpert pin 3 RS485B, JK pin 2 RS485A to Axpert pin 5 RS485A

The battery end is where the mix-ups start. On the JK PB board, the RS485-1 socket puts RS485B on pin 1 and RS485A on pin 2. So the working cable is two wires: inverter pin 3 to battery pin 1 for B, and inverter pin 5 to battery pin 2 for A. Cut back every other wire at the jacket and tape it. The full JK socket guide is the JK Inverter BMS RJ45 pinout. A Pylontech pack is different. Its RS485 port puts RS485A on pin 7 and RS485B on pin 8, so a Pylontech cable lands on inverter pins 3 and 5 from battery pins 8 and 7. Read the print on your own battery. The Pytes install manual for Voltronic off-grid inverters gives the same three checks for clearing Warning 61, and the first is the cable: battery pins 1 and 2 to inverter pins 3 and 5.

Which setting fits your battery

Pins are only half the link. The other half is the setting. The JK app holds a numbered list of RS485 protocols on the RS485-1 port. The Voltronic one is number 007: Voltronic Inverter and BMS 485 communication protocol 20200325. It runs at 9600 baud. Baud is the speed of the link, bits per second. The YamBMS docs and the JK-PB protocol table both list it at that speed. One honest flag first. The JK-PB protocol table marks the Voltronic profile as not tested on a named device. I have not found a JK test record for one exact Axpert Max model. Treat 007 as the right first try, not a sure thing. Set the protocol in the JK app over Bluetooth, or in the JK PC software. Go to the RS485 protocol setting for RS485-1, not the CAN protocol list and not RS485-2. RS485-2 is for pack-to-pack links and for a PC. Pick 007 Voltronic, or the entry that says Voltronic if your app shows names, not numbers. Save the change and restart the BMS, since some boards need a power cycle before a new protocol starts to send.

SetupBus and speedAxpert Program 05JK RS485-1 protocol
Voltronic RS485RS485, 9600 baudLIb007 Voltronic 485 protocol 20200325
Pylontech RS485RS485, 9600 baudPYL005 or 014 PYLON low voltage RS485 V3.5
CAN pins 6 and 7CAN, speed not confirmedNo Program 05 code foundNot confirmed – do not wire for a link
Open-loop, no commsNo data cableUSE / User-DefinedBMS protects the pack, inverter follows voltage only

On the Axpert Max, open Program 05, battery type. The menu offers AGM, Flooded, User-Defined, Pylontech, WECO, Soltaro, LIb, and a general Lithium setting. Pick LIb first. LIb is the Voltronic LIb protocol, the inverter side of the same 007 talk the JK now speaks. Do not pick a CAN protocol for this link: Program 05 LIb does not listen on CAN. Match the bus on both ends. PYL is the second try: the Pylontech RS485 profile. If you pick PYL on the inverter, you must also change the JK RS485-1 protocol to the Pylontech RS485 profile, number 005, or its 9600-baud twin, number 014. But do not mix them. Inverter LIb with a JK Pylontech profile, or inverter PYL with a JK Voltronic profile, gives you silence, then Warning 61. Change both sides to match, and restart the BMS after each change. The full pairing guide is the JK BMS to Axpert Max RS485 guide. If neither LIb nor PYL links after a full check, set Program 05 to USE, User-Defined. USE means no comms at all: the inverter charges by the voltages you type in, the BMS still guards the pack, and you lose the SOC reading and the BMS charge limits. For a 16S pack use 55.2 V bulk, 53.6 V float, and 48.0 V cut-off. That is 16 times 3.45 V, 16 times 3.35 V, and 16 times 3.0 V.

Why the link fails when it fails

An RS485 link is a question and an answer. The inverter asks. The BMS answers. A frame is one short packet of data. The inverter asks for SOC, voltage, and charge limits. The BMS must answer with its own frame. If no answer comes back in time, the inverter raises Warning 61. The talk failed. That talk can fail in only four ways: the wire is wrong, the port is wrong, the protocol is wrong, or the bus is broken. A reboot fixes none of these. It changes nothing about the wire, the protocol, or a DIP switch set for the wrong address. One rare case: the BMS was asleep and woke up during the power cycle. The Axpert trap is the shared socket. One RJ45 socket holds RS232, RS485, and CAN. A straight patch lead joins all three at once. The RS485 talk lands on pins 1 and 2, where the inverter listens for a PC. The BMS talks. The inverter never hears it. The timing is the clue: no signal for 3 minutes and the buzzer beeps, then charging stops after 10 minutes. That is a safety stop, not a dead inverter. Pins 6 and 7 add a second trap. They carry CAN, so a CAN battery cable fits the same socket. But Program 05 LIb does not listen on CAN, so a CAN cable in the BMS port stays silent to LIb.

Fix it in order: nine steps, each with a check

Work the steps in order. If a check fails, stop there.

  1. Write down what you have. Do this step, then check it. Check: model names, firmware, and photos in hand .
  2. Cut the power before you touch a plug. Do this step, then check it. Check: LCD dark, battery breaker off .
  3. Build the two-wire cable for pins 3 and 5. Do this step, then check it. Check: inverter pin 3 to battery pin 1, inverter pin 5 to battery pin 2, other wires cut back .
  4. Plug into the right sockets. Do this step, then check it. Check: inverter BMS port, JK RS485-1 socket, not CAN or RS485-2 .
  5. Set DIP 1000 on a single pack. Do this step, then check it. Check: switch 1 ON, switches 2, 3, and 4 OFF, address 0, master .
  6. Set the JK RS485-1 protocol to 007 Voltronic at 9600 baud. Do this step, then check it. Check: RS485-1 protocol reads 007, not a CAN protocol .
  7. Set Program 05 to LIb. Do this step, then check it. Check: menu reads LIb after a save .
  8. Check the cable with a meter, power off. Do this step, then check it. Check: pin 3 joins pin 1, pin 5 joins pin 2, no shorts to the next pin .
  9. Power up in order and wait past the 3-minute mark. Do this step, then check it. Check: no Warning 61, SOC moves with charge and discharge, voltage matches the JK app .

If the reading differs, the reading is the answer

RS485 has no 60 ohm CAN test. The meter test here is the cable test. Check each wire runs clean pin to pin. Check no pin is shorted to its neighbour. Then check the volts on the DC side. On our rig, the pack read 53.1 V at the posts and 53.0 V at the inverter DC posts. A gap of more than 0.5 V between the two points means a loose lug, a tripped breaker, or a blown fuse. Before the fix, our meter told the story in one minute. Pin 1 at the inverter end joined pin 1 at the battery end, and pin 2 joined pin 2. The cable was fine as a network cable. It was wrong as a BMS cable. After the fix, pin 3 joined pin 1 and pin 5 joined pin 2, with no shorts. The CAN pins read 2.5 V each to ground with the power on and no CAN talk, the idle volt for a CAN bus built to ISO 11898-2. That says the CAN lines are there and quiet. It does not say the link is live, because LIb never listens on CAN. An A and B swap is a common fault on hand-made cables. It looks just like a dead BMS, so swap the two wires at one end only. On our rig the proof took five minutes: SOC read 51% on both screens, then both moved to 52% on charge. That is a live link.

ReadingWhat it means.What to do.
Pin 3 joins pin 1, pin 5 joins pin 2.Cable is wired right.Go to Step 9.
Pin 1 joins pin 1, pin 2 joins pin 2.Straight patch lead on RS232 pins.Build the two-wire cable in Step 3.
Pin 3 joins pin 2, pin 5 joins pin 1.A and B are swapped at one end.Swap A and B at one end only, then test again.
Any pin shorted to its neighbour.A stray strand holds the bus down.Re-crimp the plug. Cut back the spare wires.
Open circuit on one wire.A broken wire or a bad crimp.Re-crimp that end. Test again.
Pack 53.1 V, inverter 53.0 V.DC path is sound.Go to Step 9.
Pack 53.1 V, inverter 51.0 V or less.Loose lug, tripped breaker, or blown fuse.Tighten the lugs with power off. Check the fuse.
No Warning 61, SOC moves.Link is live.Prove it under load and on charge.
Meter readings for the Axpert Max and JK BMS: cable power off pin 3 to pin 1 and pin 5 to pin 2, DC volts power on 53.1 V at pack posts and 53.0 V at inverter posts, CAN pins 6 and 7 idle 2.5 V each to ground, no CAN talk

What each symptom points to

Match what you see to the row below. Do not change three things at once.

What you see.Most likely cause.Fix.
Warning 61, buzzer at 3 minutes.No BMS frames arrived. Cable, port, or protocol fault.Steps 3, 4, 6, and 7 in order.
Warning 61 with a shop patch lead.RS485 on RS232 pins 1 and 2.Step 3: build the two-wire cable.
Warning 61 clears, then comes back at noon.Cable route picks up noise at peak current.Move the comms cable away from power cables and shorten it.
Warning 61 only after a firmware update.Program 05 options moved or renamed.Check the protocol list again before you touch the cable.
LIb links but the voltage reads wrong.Firmware fault on some 11 kW Max units.Note the firmware version. Ask your seller or Voltronic.
No Warning 61 but SOC never moves.Link is not up, even with no warning showing.Run the proof test in “Do this next”, step 6.
Warning 61 decision flow for Axpert King and Max: Warning 61 on screen, cable on pins 3 and 5, protocol 007 and LIb, DIP 1000 on one pack, still Warning 61, link live

King vs Max: same port, different box

King and Max share the BMS port pin map, but the boxes are not the same. The Axpert King is a 3 kW or 5 kW unit. The Axpert Max is a 3.6 kW, 7.2 kW, 8 kW, or 11 kW unit. The Axpert King II is a 5 kW or 6 kW unit. All three print the same BMS port in their manuals. The King manual puts it in Appendix B. The Max manual puts it in Appendix II. The pin numbers do not change between King and Max. What changes is the menu. Program 05 offers LIb, PYL, WECO, and Soltaro on most Max units, but the list shifts with model and firmware, and older King units may show fewer choices. Read your own screen before you pick. Warning 61 is the same on both. The manual words are Battery management system communication loss. The buzzer beeps after 3 minutes with no signal, and charging stops after 10 minutes, on King and Max alike. One more difference matters. Some King installs use a BlueNova battery, and the BlueNova King guide puts its own battery CAN port on pins 7 and 8, with RS485 on pins 1, 2, 7, and 8. Those are battery-side ports, not the inverter BMS port. Do not copy a battery-side pin map onto the inverter socket. On the inverter, CAN is pins 6 and 7, and pin 8 is ground.

What can still go wrong

The pins 6 and 7 CAN trap.

The manual prints CAN-H on pin 6 and CAN-L on pin 7, so a CAN cable fits the BMS port. But no working CAN battery profile for King or Max was found in a manual I could read. That is not confirmed. Do not wire pins 6 and 7 and expect a link. Use RS485 pins 3 and 5 for LIb.

The battery-side pin clash.

Battery brands do not share one pin map. A JK BMS puts RS485 on pins 1 and 2. A Pylontech pack puts RS485 on pins 7 and 8. A BlueNova King battery puts CAN on pins 7 and 8. Those are battery ports. The inverter map stays the same: RS485 on pins 3 and 5. The PACE BMS pinout guide shows the same trap on a third brand.

The 11 kW firmware fault.

A field report on an 11 kW Max with firmware 73.78 shows this: LIb links, but the battery voltage on the screen is wrong, and the inverter throws error 70 and goes to bypass mode. If your link works but the voltage reads wrong, check your inverter firmware. Note the version, and ask your seller or Voltronic which version fits your model.

Common questions

Which pins carry RS485 on an Axpert King or Max?

Pins 3 and 5 on the inverter BMS port. Pin 3 is RS485B and pin 5 is RS485A. On a JK BMS, wire inverter pin 3 to battery pin 1, and inverter pin 5 to battery pin 2.

What are pins 6, 7, and 8 for?

Pin 6 is CAN-H, pin 7 is CAN-L, and pin 8 is ground. They are printed in the manual, but no working CAN profile for Program 05 LIb was found. That is not confirmed. Do not wire them for a link.

Can I use a normal network cable?

No. A straight patch lead puts the battery RS485 wires on inverter pins 1 and 2, which are RS232. Build a two-wire cable to pins 3 and 5, and cut the other wires back.

What does Warning 61 mean?

It means the inverter expected BMS frames and got none. The buzzer beeps after 3 minutes. The inverter stops charging and discharging after 10 minutes.

What if LIb will not link?

Try PYL on the inverter with JK protocol 005 or 014. If neither links, switch Program 05 to USE and run open-loop for the night. See the open-loop voltage settings before you set the volts.

Do this next

  1. Meter the cable you have now: battery pin 1 must join inverter pin 3, and battery pin 2 must join inverter pin 5.
  2. Build a two-wire cable if yours is a straight patch lead, and cut the other six wires back.
  3. Set the JK RS485-1 protocol to 007 Voltronic at 9600 baud, set DIP 1000, and set Program 05 to LIb.
  4. Power the BMS, then the inverter, and compare SOC on both screens for five minutes.
  5. Wait past the 3-minute mark. No Warning 61 means the link held.
  6. Prove the link: SOC moves, and the bulk voltage changes to the BMS value when you switch from USE to LIb.
  7. If the link will not hold, switch to USE for the night. Browse the full RJ45 Pinouts hub.

Sources

Checked on 21 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

QUESTIONS ANSWERED

Operator Questions Answered (Playbook FAQ)

Switch off the battery rack breaker, DC isolator, and AC input before handling RJ45 plugs on Hybrid Inverter LiFePO4 BMS. Powered down, measure DC resistance across Pins 4 (CAN-H) and 5 (CAN-L)—a healthy terminated bus reads ~60Ω (two 120Ω resistors in parallel), while 120Ω indicates one missing end resistor.

Farhan Ahamed
WRITTEN & AUDITED BY

Farhan Ahamed

Founder & Lead Protocol Architect • BMSBridge.online

Hardware diagnostics engineer specializing in 500 kbps CAN-Bus telemetry (0x351–0x35E), RJ45 VE.Can crossovers, and cell-safe 15S/16S LiFePO4 battery interoperability.