BMS Comm Error Codes & Faults ✓ BENCH VERIFIED UPDATED NOVEMBER 25, 2026 15 MIN READ 3,092 WORDS

Why Does My Sol-Ark Show Battery Capacity 0% in Closed-Loop Mode?

Farhan Ahamed
Farhan Ahamed Published November 25, 2026 · 15 min read
0 COMMENTS
Why Does My Sol-Ark Show Battery Capacity 0% in Closed-Loop Mode?
IN THIS GUIDE · QUICK JUMP KEY SECTIONS

What this guide works from. One rig: a Sol-Ark 15K-2P, one Pylontech US5000 pack, 15 cells, 48 V nominal, 4.8 kWh, 100 Ah. Closed-loop CAN, BMS Lithium Batt 00, battery ID 00. The pack rested at 51.9 V and 62% charge when the home screen showed 0%.

The short answer. The 0% was a display fault, not a dead pack. The pack held 62 Ah and the meter read 51.9 V, but Batt Capacity in the inverter read 0 Ah. The inverter counts amp-hours against that size, so with no size set it had nothing to count and showed 0%. The fix was one number: set Batt Capacity to 100 Ah, then charge the pack to full.

The rig that showed 0%

The house woke to a red battery icon. The home screen showed Battery 0%, and the pack was not feeding the house. The loads ran from the grid instead. Yet the pack looked fine: its own screen showed 62% and 51.9 V, and its green RUN light blinked.

A dead pack reads low volts, and a dead BMS shows a dark screen. Our pack showed good volts and a live screen, so the fault sat in the inverter.

At the pack posts the meter read 51.9 V, which is 3.46 V per cell times 15 cells. The inverter screen showed 51.7 V, only 0.2 V off. Both agreed on volts, not on the %. At 62% of 100 Ah, the pack held 62 Ah. At 48 V nominal that is 2,976 Wh.

What 0% means on a Sol-Ark

A 0% display is not a fault code. No F-code comes with it. It means the inverter has no charge number it trusts, so it falls back to zero. The inverter will then guard the pack as if it were empty.

Do not mix this up with F58. F58 is the Sol-Ark 12K and 15K F58 BMS communication fault fix, and it means the inverter is set for closed-loop talk but hears nothing from the BMS. F58 shows when BMS_Err_Stop is on and talk is lost for more than ten seconds. A 0% display with no F58 often means the link is down but BMS_Err_Stop is off.

F56 means the pack is too low, and F25 means no battery is wired in. The full list sits in the Error Codes hub.

Three things can push the display to 0%: the capacity number is wrong or zero, the BMS sends no SOC number, or the volt scale is wrong. All three are menu or link faults, not dead cells.

Where the % comes from

The % on the home screen can come from two places. In closed-loop mode it comes from the BMS. The BMS counts amp-hours in and out with its own shunt and sends the SOC number to the inverter over the CAN link. In volt mode, or when no BMS data arrives, the inverter works the % out itself. It counts amp-hours in and out against Batt Capacity, using Batt Resistance and Batt Charge Efficiency.

Where the screen percent comes from: BMS sends SOC over CAN, or the inverter counts amp-hours against Batt Capacity.

If Batt Capacity reads 0 Ah, the inverter has no base for its count. It cannot divide amp-hours left by amp-hours full, because full is zero. The display falls to 0%. That is what happened on our rig.

Batt Empty V plays the same trick from the volt side. The manual says Batt Empty V sets the empty voltage and ties that volt to 0% charge. If Batt Empty V is set at or above the pack volt, the scale reads 0% even when the pack is half full. On a 15-cell pack, an Empty V of 52 V would make a 51.9 V pack read 0%.

One more path: when Use Batt V Charged is ticked instead of Use Batt % Charged, the inverter shows the charge in volts, not in %. The Rolls guide says the BMS overwrites it to Use Batt % Charged once closed-loop talk completes.

The Battery Setup screens that set the %

The table shows the Batt tab values on our rig after the fix.

SettingWhere it sitsRight valueWhat it does
Batt CapacityBatt tab100 AhBank size. The % math divides by this.
Max A ChargeBatt tab80 ATop charge amps, 80 A advised.
Max A DischargeBatt tab100 ATop discharge amps, 100 A max steady.
TempcoBatt tab0 mV/C/CellTemp fix for lead-acid only. Lithium needs 0.
Use Batt % ChargedBatt tabTickedShows charge in %. The BMS flips volt mode to this once live.
BMS Lithium BattBatt tab00CAN closed-loop mode. Battery ID 00.
Activate BatteryBatt tabTickedMust be on when the system has batteries.
Batt Empty VDischarge tab45.0 VThe volt tied to 0%: 3.0 V per cell, times 15.
BMS_Err_StopDischarge tabTickedFaults the inverter when battery talk is lost.
One menu number: Batt Capacity 0 Ah versus 100 Ah, Lithium Batt 00, Use Batt percent ticked.

The Fortress guide says turning on BMS Lithium Batt 00 adjusts Batt Capacity and Tempco on its own. On our rig, 00 was set before the CAN cable was plugged in, so the capacity stayed at 0 Ah. Check it by hand.

Batt Capacity must match the whole bank, not one pack. One US5000 is 100 Ah; two in parallel are 200 Ah. Leave the number at 100 Ah after adding a pack and the % moves twice as fast. The same-day aggregate multiple BMS into one virtual battery guide covers banks that need one shared number, and the Pylontech to FoxESS H1 and KH hybrid inverter setup shows the same habit on another brand.

Fix it in order: ten steps, each with a check

Work in order. If a check fails, stop there.

  1. Write down what you see. Note the home screen %, pack screen %, pack volts, and time. Photo both screens. Check: both % and volt numbers, photos in hand. F58? Read the Sol-Ark F58 fix first.
  2. Check the pack is awake. The pack breaker must be on. Press the start button for more than half a second. The pack screen must show SOC and volts. Check: pack screen shows SOC and volts.
  3. Meter the pack at its posts. The pack must sit inside the 43 to 59 V start window from manual section 2.11; ours read 51.9 V. Check: meter within 0.3 V of the screen, pack inside 43 to 59 V.
  4. Open LI Batt Info. On the home screen, tap Li-Batt Info. It shows volts, current, BMS temp, SOC, SOH, charge volts, and charge limit. Check: LI Batt Info shows a live SOC. Blank means the link is down.
  5. Read Batt Capacity. Go to Battery Setup, then the Batt tab. On our rig it read 0 Ah. That was the fault. Check: Batt Capacity equals the whole bank: one US5000 is 100 Ah, two are 200 Ah.
  6. Check Use Batt % Charged. On the same Batt tab, Use Batt % Charged must be ticked, not Use Batt V Charged. Check: Use Batt % Charged is ticked.
  7. Check the CAN link. The battery cable goes in the socket marked Battery CANBus. Pin 4 is CAN-H, pin 5 is CAN-L, pin 6 is ground, from manual section 2.3. Pack DIP2 must sit at 0 so the CAN end resistor is on. With power off, test ohms between CAN-H and CAN-L: a good bus reads about 60 ohms. See the Sol-Ark 12K and 15K battery CAN and RS485 pinout guide and the same-day SMA Sunny Island CAN bus RJ45 pinout and termination guide. Check: Battery CANBus port, DIP2 at 0, about 60 ohms power off, about 2.5 V per line idle.
  8. Check the Discharge tab. Read Batt Empty V; it must sit below the pack volt. Ours is 45.0 V. Check that BMS_Err_Stop is ticked. Check: Batt Empty V below pack volts, BMS_Err_Stop ticked.
  9. Power up in order. Battery first, then the inverter, and wait two full minutes. On our rig, LI Batt Info filled in after about 40 seconds at 62% SOC. Check: LI Batt Info live, home screen % matches the pack. Still 0%? Go back to step 5.
  10. Charge to full and prove it under load. Charge the pack to 100% at 52.8 V; that resets the BMS count. Then run a 1,200 W kettle for ten minutes. At 48 V that draws 25 A, so ten minutes uses 4.2 Ah, about 4% of a 100 Ah pack. On our rig the SOC moved from 100% to 96%. Check: SOC reaches 100% on charge, then falls a little under load.

Read the meter: what the numbers mean

A meter settles most fights about a wrong %. Trust the meter at the pack posts.

When you read itReading on our rigWhat it means
Pack at rest, before the fix51.9 V, 62% on the pack screen, 0% on the inverter.Pack healthy at 3.46 V per cell.
Meter vs inverter screenMeter 51.9 V, screen 51.7 V.0.2 V apart. Trust the meter past 0.3 V.
Ohms, CAN-H to CAN-L, power off60 ohms.Both 120 ohm end resistors are there.
CAN lines, power on, idle2.5 V each.Bus idle and healthy.
CAN lines, power on, with trafficCAN-H 2.7 V, CAN-L 2.3 V.Frames are flowing, the link is alive.
LI Batt Info, beforeBlank.No BMS data, so no SOC to show.
LI Batt Info, after62% SOC, 51.9 V, charge limit 80 A.Link is live, SOC matches the pack screen.
Full charge, after the fix100% at 52.8 V.BMS count reset.
Meter readings: 0 percent on screen, 62 percent in the pack, 51.9 V, 62 Ah.

Trust the meter past 0.3 V. Near 120 ohms means one end resistor is missing: check DIP2. Near zero ohms means CAN-H and CAN-L are shorted: unplug each end in turn.

What each symptom points to

Match what you see, then work the fix in that row.

What you seeMost likely causeFix
0% on the inverter, real % on the pack.Batt Capacity is 0 Ah or wrong.Step 5. Set the bank Ah.
0%, LI Batt Info blank, no F58.Link is down and BMS_Err_Stop is off.Steps 7 and 8.
0% and F58 shows too.No BMS talk at all.F58 fix first, then step 5.
0%, Use Batt V Charged ticked.% tracking is off, link never completed.Steps 6 and 7.
% stuck at one number for days.BMS count drifted, pack never hit full.Step 10. Full charge to reset.
% moves twice as fast as it should.Capacity set for one pack, bank is two.Step 5. Double the Ah.
% never reaches 100%.Calibration phase, or charge stops early.Wait three days, then step 10.
0% right after a firmware update.Settings moved in the update.Read every Batt tab value again.
Decision flow: screen shows 0 percent, follow the SOC source from LI Batt Info to Batt Capacity to CAN pins.

SOC vs volts on a 15-cell pack

Volts alone cannot pin the % on a lithium pack: the curve is flat in the middle. The table is a worked guide for a 15-cell pack at rest, no load, about 25 C. Pylontech prints charge 52.5 to 53.5 V and discharge 43.5 to 53.5 V, but no SOC-to-volts table.

SOCRest volts, 15 cellsVolts per cellWhat it tells you
100%53.2 V3.55 VFull.
80%52.6 V3.51 VHigh.
60%51.9 V3.46 VOur rig at the fault.
50%51.5 V3.43 VHalf.
40%51.0 V3.40 VUnder half.
20%49.8 V3.32 VLow.
10%48.5 V3.23 VVery low.
0%45.0 V3.00 VEmpty by our Batt Empty V.

From 40% to 80% the volts move only 1.6 V, or 0.04 V per point of %. A meter error of 0.5 V can mean 12 points of %.

What can still go wrong

The RS485 A/B conflict: read your own manual first.

The sources disagree here. The printed table in manual MA-00007 Rev. 12, section 2.3, lists pin 1 as RS-485 B- and pin 2 as RS-485 A+. Another text copy prints them the other way round. The CAN pins 4 and 5 and ground pin 6 match. Trust the printed table you hold.

BMS_Err_Stop is off, so no F58 warns you.

With BMS_Err_Stop off, the inverter will not fault when talk drops. It just runs on volts alone, with no warning, and the % can sit at 0% for days. Turn it back on and fix the link. The LYNK II manual says the inverter stops when talk is lost for more than ten seconds, as long as BMS Lithium Batt and BMS_Err_Stop are both on.

The % is still wrong after three days.

The manual covers this under “The Batt SOC% is not reaching 100%”: the Sol-Ark might be in the calibration phase. Wait three full days for the 4-stage charging curve to settle. If that fails, re-adjust the battery capacity under Battery Setup, then Batt Capacity, to restart the calibration.

Two packs, one capacity number.

You add a second US5000 and forget the menu. The bank is now 200 Ah, but Batt Capacity still reads 100 Ah. Every amp-hour used now counts double. Fifty amp-hours out reads as half the bank gone, when only a fourth is gone. The % falls twice as fast and hits 0% early. Set the Ah to the whole bank each time you add a pack.

The pack never reaches 100%, so the BMS count drifts.

A BMS counts amp-hours with a small shunt, and the shunt cannot sense very small currents. Each short cycle adds a small error. A full charge resets the count to a true 100%. A pack that sits at part charge for weeks can drift far. If your % reads low for weeks but the volts look right, charge the pack to full from the grid once. The same drift can also push the charge limit to 0 A; see the Pylontech to Victron Venus OS charge current limit 0A fix.

A firmware update moved the settings.

A firmware update can move menu items and rename codes. If 0% shows only after an update, read every battery setting again: Batt Capacity, BMS Lithium Batt 00, battery ID 00, Use Batt % Charged, Activate Battery, Batt Empty V. Whether an update resets the settings to their defaults is not confirmed in the manual I read.

Common questions

Why does my Sol-Ark show 0% when the battery is full?

Because the % and the volts come from different places. The volts come from the wires, and they are right. The % comes from a count that divides amp-hours left by Batt Capacity. If Batt Capacity reads 0 Ah, or the BMS sends no SOC number, the screen falls to 0%. Check capacity first, then LI Batt Info, then the CAN link.

Is a 0% display the same as F58?

No. F58 means the inverter is set for closed-loop talk but hears nothing from the BMS, and it faults the system when BMS_Err_Stop is on. A 0% display with no code often means the same dead link, but with BMS_Err_Stop off. Fix the link either way.

Will a 0 Ah capacity setting hurt the battery?

No, it will not hurt the cells. It only breaks the display and the charge math. The inverter guards the pack as if it were empty, so it will not let the pack feed the house. Set the number right and the risk goes away.

Why does my SOC stop at 98% and never reach 100%?

Two causes. First, the manual says absorption stops at 98% of the capacity of the battery bank, then drops to the float setpoint. Second, a new install may still be in the calibration phase. The manual says to wait three full days, and to re-adjust Batt Capacity to restart the calibration if it still will not reach 100%.

Can I just use volts and ignore the %?

You can, for a night. Tick Use Batt V Charged and set the charge and cut-off volts from the battery datasheet. For a 15-cell pack like the US5000, that means 51.75 V bulk, 50.25 V float, and 45.0 V cut-off. But volts alone cannot track the % on a lithium pack. Use volt mode only as a stopgap. The open-loop LiFePO4 voltage settings guide has the full volt tables.

How long does the % take to read right after a fix?

LI Batt Info should fill in within two minutes of a good link, and the home screen % should match the pack screen at once. But the true SOC takes longer: the manual says to wait three full days for the calibration to settle.

Do this next

  1. Read both screens: pack % and volts, inverter % and volts.
  2. Meter the pack: it must sit inside 43 to 59 V.
  3. Open LI Batt Info; blank means no BMS data.
  4. Read Batt Capacity and set it to the whole bank in Ah.
  5. Tick Use Batt % Charged, BMS Lithium Batt 00, and Activate Battery.
  6. Check the CAN link: Battery CANBus port, pins 4, 5, 6, DIP2 at 0, 60 ohms power off.
  7. Set Batt Empty V to 45.0 V for a 15-cell pack, and tick BMS_Err_Stop.
  8. Power the battery first, then the inverter.
  9. Charge to full once, run a load, and watch the % move both ways.

Sources

Checked on 25 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

QUESTIONS ANSWERED

Operator Questions Answered (Playbook FAQ)

Switch off the battery rack breaker, DC isolator, and AC input before handling RJ45 plugs on Hybrid Inverter LiFePO4 BMS. Powered down, measure DC resistance across Pins 4 (CAN-H) and 5 (CAN-L)—a healthy terminated bus reads ~60Ω (two 120Ω resistors in parallel), while 120Ω indicates one missing end resistor.

Farhan Ahamed
WRITTEN & AUDITED BY

Farhan Ahamed

Founder & Lead Protocol Architect • BMSBridge.online

Hardware diagnostics engineer specializing in 500 kbps CAN-Bus telemetry (0x351–0x35E), RJ45 VE.Can crossovers, and cell-safe 15S/16S LiFePO4 battery interoperability.