CAN Bus, RS485 & RJ45 Pinouts ✓ BENCH VERIFIED UPDATED NOVEMBER 21, 2026 15 MIN READ 3,253 WORDS

Which PACE Port Takes the Inverter Cable? CAN, RS485 or RS232?

Farhan Ahamed
Farhan Ahamed Published November 19, 2026 · 15 min read
0 COMMENTS
Which PACE Port Takes the Inverter Cable? CAN, RS485 or RS232?
IN THIS GUIDE · QUICK JUMP KEY SECTIONS
01 · KEY SECTION Jump ↓

The rig that would not link

It was a new build, and it looked right. The Deye 8 kW sat…

02 · KEY SECTION Jump ↓

What the pins carry

PACE is a BMS maker, not a battery brand. A BMS is the battery…

03 · KEY SECTION Jump ↓

Which setting fits your battery

Pick the bus first, then the port, then the profile. If your inverter speaks…

04 · KEY SECTION Jump ↓

Why the pin order matters

A dead PACE link is a handshake fault. A handshake is the short exchange…

05 · KEY SECTION Jump ↓

Fix it in order: nine steps, each with a check

Work the steps in order. If a check fails, stop there.

06 · KEY SECTION Jump ↓

If the reading differs, the reading is the answer

A meter can rule out a dead link in minutes. It cannot read CAN…

07 · KEY SECTION Jump ↓

What each symptom points to

Step-by-step field verification & diagnostic reference inside this section.

08 · KEY SECTION Jump ↓

Pins 4 and 5 on the RS485 port: not verified

Here is the one place where this guide stops and says so plainly. The…

09 · KEY SECTION Jump ↓

When the link will not hold, run on volts

If the link will not come up tonight, run open-loop for the night. Do…

10 · KEY SECTION Jump ↓

What can still go wrong

Step-by-step field verification & diagnostic reference inside this section.

11 · KEY SECTION Jump ↓

Common questions

Step-by-step field verification & diagnostic reference inside this section.

12 · KEY SECTION Jump ↓

Do this next

Step-by-step field verification & diagnostic reference inside this section.

What this guide works from. One rig: a SOK 48 V 100 Ah pack with a PACE BMS, a Deye SUN-8K hybrid inverter, a 16-cell LiFePO4 pack resting at 52.8 V, the pack screen showing 52% charge, and the Deye screen showing no battery at all.

The short answer. A PACE BMS has three same-looking RJ45 ports, and each one carries a different signal. The CAN port puts CAN-H on pin 4, CAN-L on pin 5, and ground on pin 2. The RS485 port puts RS485B on pin 1, RS485A on pin 2, and a second RS485 pair on pins 7 and 8. The RS232 port is for a PC running PbmsTools, the free PACE software, not for an inverter. On our rig, the cable sat in the RS485 port while the inverter waited for CAN. We moved one plug to the CAN port, set the Pylontech CAN profile, and the Deye showed 52% SOC within two minutes.

The rig that would not link

It was a new build, and it looked right. The Deye 8 kW sat on the wall, and the SOK pack sat below it. The pack read 52.8 V: 3.30 V per cell, times 16 cells. The pack screen showed all 16 cells between 3.29 V and 3.31 V, and 52% charge. Then the inverter was switched on. The Deye home screen showed pack volts, but no SOC and no battery data. State of charge, or SOC, is how full the battery is.

What the pins carry

PACE is a BMS maker, not a battery brand. A BMS is the battery brain: it watches cells, sets charge limits, and guards the pack. PACE boards sit inside batteries sold under other names, such as SOK, Jakiper, EG4 LifePower4, Hubble AM-2, and LBSA. If your battery opens with PbmsTools, or its BMS screen shows PACE firmware, this guide is for you. A PACE rack battery often shows four things on the front panel: CAN, RS485, RS232, and a DIP switch block, plus a small screen on some. DIP switches are small on-off switches that set the battery address. The CAN and RS485 ports sit side by side in the same RJ45 shell. The print is small and wears off, so check the battery manual for your exact model.

PortPinWhat it does.
CAN4CAN-H, CAN data high line.
CAN5CAN-L, CAN data low line.
CAN2Ground, if your inverter wants it.
CAN1, 3, 6, 7, 8Not connected.
RS4851RS485B, B- side, pair 1.
RS4852RS485A, A+ side, pair 1.
RS4853, 6Ground.
RS4857RS485A, A+ side, pair 2.
RS4858RS485B, B- side, pair 2.
RS4854, 5Not verified. Do not wire to them.
RS232—Serial to a PC. PbmsTools only.

Wire CAN-H to CAN-H on pin 4, and CAN-L to CAN-L on pin 5, one twisted pair only: the blue pair in T-568B, the common wire color order for RJ45 plugs. The ground on pin 2 is there for inverters that need a CAN ground point. Run the ground wire only if your inverter manual shows a ground pin. Do not run an 8-wire patch cable. The other pins are not connected on the PACE side, but a full cable can still join signals on the inverter side that should never meet. The full Deye side of the link is the Deye & Sunsynk BMS port pinout.

PACE BMS — CAN port pin map

Which setting fits your battery

Pick the bus first, then the port, then the profile. If your inverter speaks Pylontech CAN, use the CAN port, pins 4 and 5, and set the Pylontech CAN profile in PbmsTools. If it speaks Pylontech RS485, use the RS485 port, pins 1 and 2, and set the Pylontech RS485 profile. If your inverter is a Voltronic Axpert, use the RS485 port and the profile your Axpert manual names, usually LIb or PYL. If it is a Deye, use the CAN port with Lithium Mode 00. The profile and the port have to agree, and the inverter setting has to agree with both. CAN runs at 500 kbps on the Pylontech profile. A PACE spec sheet for the P16S100A board gives 500K as the CAN default speed and 9600 bps as the RS485 default. Check your manual or the PbmsTools protocol screen first. A wrong speed looks just like a dead cable.

Battery and inverterLink and portInverter settingBMS profile
PACE pack with Deye 8 kWCAN, CAN port pins 4 and 5.Lithium Mode 00.Pylontech CAN.
PACE pack with Growatt SPF 5000 ESCAN, CAN port pins 4 and 5.Program 05 LI, Program 36 L52.Pylontech CAN.
PACE pack with Solis S6CAN, CAN port pins 4 and 5.Lithium, Pylontech CAN.Pylontech CAN.
PACE pack with Voltronic AxpertRS485, RS485 port pins 1 and 2.Program 05 LIP or LIL.PACE or Pylontech RS485.

Voltronic inverters have their own names for the PACE profiles. The Voltronic manual lists Program 05 options for lithium batteries by brand. LIP means PACE on RS485. LIL means Pylontech on RS485. Pick the one that fits the protocol you set in PbmsTools. Pick the wrong one and the inverter will not read the pack, even with the right cable and the right pins. Two more facts from the same manual are worth knowing. When the battery type is set to LIB-485, settings 12, 13, and 29 show in percent, not in volts. When comms fail in that mode, the inverter cuts the output. That is why a PACE pack on the wrong Voltronic setting can look like a dead battery. The full Axpert pairing is the JK BMS to Voltronic Axpert Max RS485 setup.

PACE BMS — RS485 port pin map

Why the pin order matters

A dead PACE link is a handshake fault. A handshake is the short exchange where two units agree they can talk. The inverter sends a frame on the CAN bus: one short packet of data. The BMS must answer with its own frame: SOC, charge limit, cell volts, temps, alarms. If no answer comes back in time, the inverter shows no battery and stops trusting the pack. The talk failed. That talk can fail in only four ways: the wire is wrong, the port is wrong, the profile is wrong, or the bus is broken. A reboot fixes none of these. It changes nothing about the wire, the profile, or a DIP switch set for the wrong address. One rare case: the BMS was asleep and woke up during the power cycle. That is luck, not a fix.

CAN works as a pair. CAN-H and CAN-L are two wires that move in step, one up and one down. The twist in the pair cancels noise from near wires. That is why the two CAN wires must sit on the same twisted pair in the cable, most often the blue pair in T-568B, pins 4 and 5. If CAN-H and CAN-L are swapped, each line still sits near 2.5 V at rest. The meter looks fine, but no frame gets through. The bus is dead, and the volts lie to you.

The three-port trap is the one that bites PACE owners. The CAN, RS485, and RS232 sockets sit side by side and take the same plug. A CAN cable in the RS485 port hears nothing, because pins 4 and 5 on that port are not CAN pins. An RS485 cable in the CAN port hears nothing too. Both give the same sign: the inverter shows no battery, while the BMS looks fine on its own screen. Check the port label, the profile, and the DIP address, in that order.

Fix it in order: nine steps, each with a check

Work the steps in order. If a check fails, stop there.

  1. Write down what you have. Note the inverter model, battery brand, and BMS model from PbmsTools. Photograph the front panel ports and the DIP switches. Check: model names and photos in hand.
  2. Read the pack on the PC first. Plug the RS232 lead into the PC port, open PbmsTools, and read the cells, temps, and alarms. If PbmsTools cannot read the pack, the fault is the cable, the driver, or the port. No inverter protocol change will fix that. Check: PbmsTools shows live cell volts.
  3. Cut the power before you touch a plug. Switch the battery breaker, DC isolator, and AC breaker off. Wait until the inverter screen is dark. Check: screen dark, battery breaker off.
  4. Check the port label, then the cable. Read the label on the socket: CAN, RS485, or RS232. For CAN, wire pin 4 to pin 4 and pin 5 to pin 5, one twisted pair only. On our rig, this was the fault: the plug sat in the RS485 port while the Deye waited for CAN, so we moved it to the CAN port. Check: plug in the CAN port at the BMS end and the BMS port at the inverter end.
  5. Set the profile in PbmsTools. Open the software, connect on the RS232 port, go to System Config, then Inverter Protocol, then the CAN Protocol setting. Pick Pylontech CAN for a Deye. Write it to the BMS and restart the battery. The write password the Bimble guide lists for this step is Pz# 168178. Check: profile reads Pylontech CAN after the restart.
  6. Set the DIP address. For one pack, or the master pack in a bank, the address is 1: the first switch up and the rest down. That setting comes from DIY Solar Forum field reports on PACE packs. The master is the pack that talks to the inverter. Do not set two packs to address 1. Check: DIP reads address 1 on a single pack.
  7. Set the inverter. On the Deye, pick Lithium Mode 00. On a Growatt, set Program 05 to LI and Program 36 to L52. On a Voltronic, pick LIP for a PACE profile or LIL for a Pylontech profile. Check: inverter setting still reads your code.
  8. Test the bus with a meter. With all power off, test ohms between CAN-H and CAN-L. A good bus reads about 60 ohms (two 120 ohm end resistors in parallel). With power on and the bus idle, test each line to ground: each should sit near 2.5 V DC. On our rig, the power-off test read 61 ohms after the plug move, and the idle test read 2.5 V on each line. Check: about 60 ohms power off, about 2.5 V per line power on.
  9. Power up in order and watch for five minutes. Switch the battery on first, then the inverter, and wait two full minutes. On our rig, the Deye showed 52% SOC after about 40 seconds, the same number the pack screen showed. Put a load on and watch the SOC move, then write the settings on a note inside the battery box door. Check: SOC agrees on both screens for five minutes.
Fix a PACE link in order

If the reading differs, the reading is the answer

A meter can rule out a dead link in minutes. It cannot read CAN frames, but it can tell you if the bus is shorted or open. All volt numbers are DC to ground, on a fast CAN bus built to ISO 11898-2. On a live bus with traffic, a plain meter shows the average: CAN-H reads 2.6 to 3.0 V and CAN-L reads 2.0 to 2.4 V. Only an oscilloscope shows the true peaks: CAN-H toward 3.5 V, CAN-L toward 1.5 V. You do not need one here.

ReadingWhat it means.What to do.
About 60 ohms, power off.Both 120 ohm end resistors are there.Go to Step 9.
Near 120 ohms, power off.One end resistor is missing.Check the BMS end resistor.
Open circuit, power off.No termination, a broken wire, or the plug is in a port with no CAN pair.Check the port first, then test the cable.
Near zero ohms, power off.A short between CAN-H and CAN-L.Unplug each end in turn. If the short stays with the cable, replace the cable.
2.5 V on each line, power on, idle.Bus idle and healthy, but nobody is talking.Check the profile and the BMS power.
2.6–3.0 V on CAN-H, 2.0–2.4 V on CAN-L.Traffic is flowing. The link is alive.Go to Step 9.
0 V or pack volts on one line.That line is shorted, or the signal chip is dead.Stop. Unplug the BMS end. If the line clears, the fault is in the BMS.

For RS485, the same idea holds with different pins. Flipped A and B is a common fault on third-party cables. If RS485 will not link, swap A and B at one end only, then test again.

What the meter should read — PACE CAN

What each symptom points to

What you see.Most likely cause.Fix.
Inverter shows no battery, BMS screen fine.Plug in the wrong port, or wrong profile.Steps 4 and 5: match the port to the link, then set the profile.
Link drops at noon or under load.Cable run tight against DC or AC wiring picks up noise.Move the comms cable away from power cables and shorten it.
PbmsTools shows nothing on the PC.Cable, driver, or port fault on the RS232 link.Fix the driver first. Swap TX and RX and try again.
Inverter shows no battery after a profile change.BMS not restarted after the write.Restart the battery, then the inverter.
Two packs show the same address.DIP address clash in a bank.Give each pack its own address.
No battery on a Voltronic, volts fine.LIP picked for a Pylontech profile, or LIL for a PACE profile.Match Program 05 to the PbmsTools profile.

Pins 4 and 5 on the RS485 port: not verified

Here is the one place where this guide stops and says so plainly. The esphome-pace-bms project, which talks to PACE boards over RS485 with Modbus, lists the RS485 jack like this: pin 1 B-, pin 2 A+, pins 3 and 6 ground, pin 7 A+, pin 8 B-. Pins 4 and 5 on the RS485 port are not listed in that document, and I could not check what they carry from a PACE source. Do not assume they are CAN. Do not wire anything to them until your battery manual says what they are. The two pairs serve different jobs. Pins 1 and 2 are the pair you use for an inverter or for monitoring software. Pins 7 and 8 are the second pair, and on EG4 LifePower4 packs the master pack uses them to poll the other packs. That EG4 habit comes from DIY Solar Forum field reports, and whether your exact PACE pack uses pins 7 and 8 the same way is not checked from a PACE document. If you have one pack only, use pins 1 and 2 and leave 7 and 8 alone.

When the link will not hold, run on volts

If the link will not come up tonight, run open-loop for the night. Do not force a cable. Set the inverter to volt mode. Set the charge volts from the battery datasheet and the BMS limits. Let the BMS guard the pack. For a 16S LiFePO4 pack: 55.2 V bulk, 53.6 V float, 48.0 V cut-off. For a 15S pack: 51.75 V bulk, 50.25 V float, 45.0 V cut-off. A 16S pack and a 15S pack do not share the same full-charge volt. See the full volt guide in the closed-loop vs open-loop LiFePO4 settings before you set the volts. Come back to the comms link in daylight, with a meter and a fresh plug. The Deye F58 walk-through is the Deye F58 BMS fault pinout guide.

What can still go wrong

The PC link comes first.

PbmsTools needs the Microsoft .NET Framework on the PC, and the USB-to-RS232 cable needs its driver installed before the software sees the port. If PbmsTools shows no port, fix the driver first. The BMS is almost never the fault at that step. If PbmsTools still shows nothing after the driver is right, swap the TX and RX wires and try again. TX is the send wire, RX is the receive wire, and cheap USB-to-RS232 cables often get them backwards. The PACE wiring guide puts TX on DB9 pin 2, RX on pin 3, and ground on pin 5, but forum users had to flip TX and RX before the software saw the pack.

The DIP all-off trap.

If all DIP switches are off and the pack still stays silent, set DIP 1 on for the first pack. Some users found the software does not like all switches off. That tip sits in field notes, not in a PACE book. Treat it as a lead, not a rule. If RS485-1 stays silent, try RS485-2. One user with a Fogstar cable found RS485-1 dead and RS485-2 worked at once. With more than one pack, plug the PC lead into pack 1, the first pack.

The cable that worked yesterday.

A comms cable run tight against DC lugs or AC wires can pick up noise when current peaks. That is why a fault that clears in the morning can come back at noon. If the link drops under load, move the cable and shorten it.

Common questions

Which PACE port takes the inverter cable?

CAN or RS485, never RS232. CAN goes in the CAN port, pins 4 and 5. RS485 goes in the RS485 port, pins 1 and 2. RS232 is for a PC running PbmsTools.

Can I wire anything to pins 4 and 5 on the RS485 port?

No. What they carry is not confirmed from a PACE source. Do not wire to them until your battery manual says what they are.

Why does PbmsTools show no port?

The USB-to-RS232 driver is missing, or the .NET Framework is not on the PC. Fix the driver first. Then swap TX and RX and try again.

What is the PbmsTools write password?

The Bimble guide lists Pz# 168178 for the protocol write step. Change the profile, write it, then restart the battery.

LIP or LIL on a Voltronic?

LIP means PACE on RS485. LIL means Pylontech on RS485. Match Program 05 to the profile you set in PbmsTools.

Do this next

  1. Read the label on the port before you crimp anything. Pick the bus your inverter speaks, then the port, then the profile in PbmsTools.
  2. For CAN, wire pin 4 to pin 4 and pin 5 to pin 5, with ground on pin 2 if your inverter wants it. For RS485, wire pin 1 to B and pin 2 to A, and leave pins 7 and 8 alone on a single pack.
  3. Set DIP address 1 on a single pack. Set the inverter to Lithium Mode 00 on a Deye, or L52 on a Growatt.
  4. Test the bus: about 60 ohms with power off, about 2.5 V per line with power on and idle.
  5. Power the BMS, then the inverter, and compare SOC on both screens for five minutes.
  6. No link tonight? Run open-loop on volts from the datasheet, and fix the link in daylight.
  7. Still stuck? Call the battery maker with model names, the PbmsTools profile, the DIP address, and meter readings.

Sources

Checked on 20 November 2026. Unconfirmed items are labelled “not confirmed” in the text.

  • Bimble Solar PACE pinout sheet. CAN port pin 4 CANH, pin 5 CANL, pin 2 ground, other pins not connected. PbmsTools profiles: Victron, Pylontech, Growatt, Sofar, Solis, Goodwe. Write password Pz# 168178.
  • esphome-pace-bms project. RS485 jack: pin 1 B-, pin 2 A+, pins 3 and 6 ground, pin 7 A+, pin 8 B-. Pins 4 and 5 not listed, not confirmed. Modbus RTU, PACE-BMS-Modbus-Protocol-for-RS485-V1.3.
  • PACE P16S100A spec sheet. CAN default 500K, RS485 default 9600 bps.
  • DIY Solar Forum field reports. DIP address 1 for a single or master PACE pack. EG4 LifePower4 master polls slaves on pins 7 and 8. TX/RX flip fixes some RS232 links. DIP 1 on fixes some silent packs. RS485-2 works where RS485-1 is dead. Field-reported, not checked from a PACE document.
  • Voltronic Axpert manual. Program 05 LIP means PACE on RS485, LIL means Pylontech on RS485. LIB-485 mode: settings 12, 13, and 29 show in percent. Comms fail cuts output.
  • ISO 11898-2 CAN standard (PCBCool, Apex Control, SCADA Protocols). Idle 2.5 V per line. Dominant 3.5 V / 1.5 V. 120 ohm per end, about 60 ohms measured.
  • This site: Deye & Sunsynk BMS port pinout, JK BMS to Deye hybrid inverter protocol, JK BMS to Voltronic Axpert Max RS485 setup, Deye F58 BMS fault pinout guide, closed-loop vs open-loop LiFePO4 settings.
QUESTIONS ANSWERED

Operator Questions Answered (Playbook FAQ)

Switch off the battery rack breaker, DC isolator, and AC input before handling RJ45 plugs on Hybrid Inverter LiFePO4 BMS. Powered down, measure DC resistance across Pins 4 (CAN-H) and 5 (CAN-L)—a healthy terminated bus reads ~60Ω (two 120Ω resistors in parallel), while 120Ω indicates one missing end resistor.

Farhan Ahamed
WRITTEN & AUDITED BY

Farhan Ahamed

Founder & Lead Protocol Architect • BMSBridge.online

Hardware diagnostics engineer specializing in 500 kbps CAN-Bus telemetry (0x351–0x35E), RJ45 VE.Can crossovers, and cell-safe 15S/16S LiFePO4 battery interoperability.